7.1  Introduction

The precision dehumidifier can run for a long time and only needs very little maintenance. The maintenance of 

the  dehumidifier  is  beneficial  to  the  long-term  and  good  operation  of  the  unit.  The  frequency  of  maintenance 

depends  on  the  operating  conditions  of  the  dehumidifier  and  the  quality  of  the  installation  environment.  The 

maintenance  cycle  of  dehumidification  equipment  should  be  determined  according  to  the  environment  and 

installation  location  of  the  equipment.  Therefore,  the  recommended  maintenance  period  can  be  determined 

according to the actual situation. Improper maintenance may reduce the dehumidification performance.

7.2  Filter

The  motor  is  equipped  with  bearings.  The  service  life  of  the  bearing  is  the  same  as  that  of  the  motor,  so  no 

additional maintenance is required.

7.3  

Motor

The motor is inspected once a year to ensure that its condition is normal.

7.4  Technical Description

The  table  lists  service  schedule  of  the  general  components.  If  necessary,  please 

contact the manufacturer for more details.

The  dehumidification  equipment  is  equipped  with  an  independent  filter  device  to  treat  the  return  air.  The 

filter  device  is  installed  at  the  return  air  of  the  equipment,  so  that  the  air  that  is  about  to  enter  the 

dehumidification equipment can be cleanly filtered. The interval between cleaning or replacing the filter device 

should  be  determined  according  to  the  amount  of  dust  and  particles  in  the  air  at  the  installation  site.  It  is 

forbidden  to  operate  dehumidification  equipment  without  a  filter  device.  Because  in  this  case,  dust  and 

impurities may reduce the dehumidification performance of the equipment, and at the same time may cause the 

compressor to start frequently. It is recommended to inspect the filter unit at least once a month.

7

.

Maintenance

Name

Service Schedule

Filter

Compressor

Coil

Defrost valve

Seal

Humidity sensor

Clean or replace

Check whether it is working normally and 

whether the vibration is normal

Check the wiring and make sure the wiring is not 

loose, check for damage and overheating.

Remove the dust and debris

Check for overheating or blockage, 
check whether the ciucuit is normal 

Check for signs of damage and displacement.
If it is worn or damaged, it should be replaced.

Check whether it is working normally and 

callibrate correctly

3~6

 

months

12

 

months

8.2  Troubleshooting procedures

8.1  Troubleshooting Introduction

The purpose of this chapter is to help the operator of the unit to analyze the cause of the failure and 

master the method of troubleshooting. The control method of the precision dehumidification equipment can 

be easily connected with automatic control according to the requirements of use. In order to facilitate failure 

analysis, please refer to the circuit diagram and related materials provided with the random group.

There is a high voltage inside the dehumidification equipment. Before taking any troubleshooting 
measures, make sure that the power supply of the dehumidification unit is cut off.

There is a high temperature area (compressor) inside the dehumidification equipment, and the unit 
should be cooled down before maintenance work is carried out.

The purpose of this chapter is to help the operator of the unit to analyze the cause of the failure and 

master the method of troubleshooting. The control method of the precision dehumidification equipment can 

be easily connected to the automatic control according to the requirements of use. In order to facilitate 

failure analysis, please refer to the circuit diagram and related materials provided with the random group.

The adjustment, maintenance and repair of the unit should be carried out by qualified technicians, and 
the relevant personnel should be clearly aware of the high temperature and high pressure inside the 
dehumidification unit.

Poor dehumidification

- Filter blocked
- Reduced air flow
- Air leak

Problem

Reason

Troubleshooting

- Clean or replace the filter
- Check the supply air outlet 
   and adjust the air rate
- Check the panel and seal 

Circuit breaker tripped off

Unit does not work

No dehumidification

No dry air

- No power to controller
- Controller failure
- Phase short circuit
- Circuit breaker failure
- Unit unplugged or no 
   power to outlet.

- Check controller fuse
- Check external on/off signal
- Check main circuit breaker 
   and phase
- Check electrical parts
- Power the unit

- Check the pipe
- Open the air damper
- Replace the filter
- Set lower humidity

- Frost on the evaporator 
- Air damper not fully opened
- Filter blocked
- Humidity set too high

- Filter blocked
- Fan failure
- Phase failure
- Supply air duct blocked

- Replace the filter
- Check the fan and motor
- Check main circuit breaker 
   and phase
- Check the air duct

- Fan failure

- Check the fan and motor

8

.

Troubleshooting

29

30

Summary of Contents for DEH-3K

Page 1: ...g Dehumidi ers Any questions please contact the manufacturer or dealer in time The repair and maintenance must be conducted by certi fed professionals Please read the manual carefully and in full befo...

Page 2: ...ates actions that must be prohibited If not strictly followed it may cause serious damage to the machine or personal injury or death When a problem occurs such as a burning smell etc please turn off t...

Page 3: ...eck 5 2 2 Wiring Check 5 2 3 Controller Check 6 Controller 6 1 General 6 1 1 Controller Terminals 6 1 2 Terminals Diagram 6 1 3 Controller s Interface 6 1 4 Parameters Setting 6 1 5 Icon 6 2 Controlle...

Page 4: ...peration of the compressor discharge high temperature and high pressure gas from the exhaust port enter the condenser for cooling It becomes a low temperature and high pressure gas intercepted by a ca...

Page 5: ...e of the equipment can be easily carried out The unique defrosting device effectively guarantees the reliable operation of the dehumidifier The fan adopts a centrifugal external rotor fan steel volute...

Page 6: ...ane fins the heat exchange efficiency is increased by 20 thus to reduce the unit size and weight The high quality thermal insulation material increases the thermal insulation effect by 15 2 5 5 Thrott...

Page 7: ...t in humidity temp sensor I IPX3 55DB 60DB 65DB Mitsubishi R410A copper tubes with blue hydrophilic coated aluminum fins SUS304 25 32 32 G4 PRE Filter 1122 600 1850mm DEH 5K DEH 10K 11KW 22KW 20A 40A...

Page 8: ...led indoors During installation there should be maintenance space at the rear of the dehumidification equipment to facilitate future inspection and maintenance of the equipment For cleaning and mainte...

Page 9: ...alled at a position 1 meter to 1 5 meters above the ground in order to detect representative water in the controlled area Flat or laid at the inspection point according to the design requirements The...

Page 10: ...tdoors to extract air as fresh air and then sent to a separate space after dehumidification such as paint spray room purification room 4 1 2 Ducting for Fresh Air Dry air Wet air Wet fresh air Dry fre...

Page 11: ...idifier unit must be carried out by professional staff Otherwise the company will not be responsible for all the consequences caused Check the installed air filter device to ensure it is in a clean st...

Page 12: ...um fan speed Fan coil valve Low fan speed Humidifier Compressor Air damper open Air damper close EC motor supply fan EC motor exhaust fan 12VDC RS485 A1 RS485 B1 RS485 A2 RS485 B2 GND FAN 1 FAN 2 L N...

Page 13: ...umidity press to raise humidity 1 changed each press Long press Short press simultaneously for 5 seconds to display the run time wait for 5 seconds to exit Short press to set the available code Press...

Page 14: ...es later after achieved the set humidity and temperature only for the available system working mode F01 2 high fan speed low fan speed available High fan speed low fan speed available when H04 1 F01 3...

Page 15: ...rror code is E01 It will resume operation after the error addressed The error code is E03 It will resume operation after the error addressed if there is RS485 1 communication failure only the fan keep...

Page 16: ...unction Code Byte Read Only or Read Write Object Read Write 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes Read Write R...

Page 17: ...e to download Smartlife App 4 Open APP and select Add device 5 Slide to Auto Scan 6 Press and hold on off button for 10 seconds until LCD full display Then release the button 7 APP will discover the d...

Page 18: ...r it is working normally and callibrate correctly 3 6 months 12 months 8 2 Troubleshooting procedures 8 1 Troubleshooting Introduction The purpose of this chapter is to help the operator of the unit t...

Page 19: ...C 13 14 t s 9 5 04 8 3 KT1 KT2 04 8 4 H3Y 2 C 360S 9 5 B3 KM3 A1 A2 KT2 360S H3Y 2 C 13 14 t s 9 5 04 9 3 KT2 1 T1 04 3 1 2 T2 04 3 1 3 T3 04 3 1 KM3 KT3 04 9 4 H3Y 2 C 540S 9 5 B4 KM4 A1 A2 KT3 540S...

Reviews: