background image

8

www.danvex.fi

    Installation

3.1 

  Introduction

The  information  in  this  chapter  describes  the  work  required  to  install  the  device. 
Careful familiarization before installation will help you properly organize the installation work

.

3.2 

  Transport and storage

To guarantee the quality and reliability of each dryer, we test all devices at the factory. 
If the dryer is in storage

:

keep the original packaging

;

avoid physical damage to the equipment

;

store the dehumidifier indoors, protect it from dust, moisture and frost

.

3.3 

   Check before installation

Remove the packaging and check the equipment: if damage is found, contact the supplier/ 
manufacturer

.

3.4 

   Moving

Before starting loading and unloading, check the weight of the equipment. It is recommended 
to use lifting devices (stacker or forklift) to move the equipment. Please note that the dryer must 
only be lifted properly to avoid tipping over and damage

.

3.5 

   Place of installation and its arrangement

The dehumidifier is designed for indoor and outdoor use. To ensure proper maintenance for 
opening the service panels, it is recommended that when installing the dryer, leave a free space 
on all sides of about 800 mm. 
The minimum width of the service space must not be less than the width of the dryer

The unit cannot be placed in an explosive place, and also cannot work with air containing 
explosive substances

For outdoor installation, measures must be taken to protect against rain, snow, dust

3.6 

   Support/ foundation

The dehumidifier should be installed in a horizontal position on a level ground or platform. 
The installation location must have sufficient bearing capacity to support the weight of the 
installation. It is recommended to fix the dehumidifier to the base. Use a building level during 
installation

.

3.7 

   Duct connection

The dimensions of the process and regeneration air ducts must comply with the recommendations 
of the ISO7807 standard. The air ducts are connected using an appropriate flange, while the bolt 
diameter should not exceed 20 mm. When connecting to the duct, consider the following factors

:

to reduce static pressure losses and not reduce dehumidification performance, shorten 
the length of the air ducts if possible

;

Summary of Contents for AD-200

Page 1: ...Manual Desiccant dehumidifiers AD 200 AD 400 AD 550 rev 2 01...

Page 2: ...1 Enclosure 7 2 3 2 Conveying air circuit 7 2 3 3 Regeneration air circuit 7 2 3 4 Rotor 7 2 3 5 Rotor drive 7 2 3 6 Safety devices 7 3 INSTALLATION 8 3 1 Introduction 8 3 2 Transport and storage 8 3...

Page 3: ...thm of operation of the dryer components 16 5 MAINTENANCE 17 5 1 Introduction 17 5 2 Filters 17 5 3 Rotor 17 5 4 Gear motor 17 5 5 Heating device 17 5 6 Drive belt 17 6 TROUBLESHOOTING 18 6 1 Inspecti...

Page 4: ...ion and operation instructions Content General information about the management of the dehumidification process the principle of operation and maintenance standards system errors diagnostics and troub...

Page 5: ...he operator s responsibility for compliance with personal safety requirements at work and local safety standards During the installation and operation of equipment each employee must follow the instru...

Page 6: ...ith relative humidity below 35 and low dew point process air preparation systems single pass airflow systems manufacturing packaging storage testing and research of pharmaceutical products production...

Page 7: ...air passes through the filter into the rotor the moisture from the air is absorbed by the dehumidifying working sector of the rotor and the dehumidified air is expelled from the other side of the roto...

Page 8: ...at resistant composite material The composite material is a corrugated structure filled with a highly effective desiccant forming many small air flow channels contacting the air with a large area and...

Page 9: ...tdoor use To ensure proper maintenance for opening the service panels it is recommended that when installing the dryer leave a free space on all sides of about 800 mm The minimum width of the service...

Page 10: ...e ground or equipped with an additional inlet filter to prevent dust and debris from being sucked in The inlet must be away from possible sources of pollution such as exhaust gases steam and harmful g...

Page 11: ...t is particularly long or must be installed vertically it must be thermally insulated and a drain point provided at its lowest position The air duct outlet must be equipped with a metal grill or mesh...

Page 12: ...st be located outside the circuit to be dried Dry air must be evenly distributed in the room to be dried no duct connection to the process air inlet is required Installation diagram inside the dehumid...

Page 13: ...cal equipment must be carried out in accordance with the standards of the country in which the equipment is used and only by qualified experts It is forbidden to connect the dehumidifier to the mains...

Page 14: ...as temperature changes may affect the measurement process The scheme for connecting an external temperature and humidity sensor to the controller is shown in the general wiring diagram of the install...

Page 15: ...on of the remote sensor the lower panel displays the humidity set by the operator Hour meter displays the total running time for AD 200 and AD 550 models Ammeter displays the current in the recovery a...

Page 16: ...ork until the humidity is reaches 45 then turns off When the relative humidity level in the drying zone reaches 50 the dehumidifier will restart 3rd press buttons Setting Set 20 20 Humidity Sensor Cal...

Page 17: ...f the components is repeated manual shutdown of the dehumidifier by selecting the OFF mode middle position on the 3 position switch switching off the regeneration air heater and the working air fan th...

Page 18: ...with two independent filter elements for filtering the working and regeneration air Filters are installed at the inlet of the air duct and provide cleaning of the air entering the dehumidifier Cleani...

Page 19: ...iring is not loose Check for signs of damage and overheating Heater Remove debris and dust from the surface of the heater Rotor Check for signs of overheating and blockage Clean the dust from the surf...

Page 20: ...fuse the fan is damaged rotor damaged the electric heater is damaged check the fan and its motor check the rotor drive motor and belt check the electric heater The device does not starts no power sup...

Page 21: ...nt A 6 10 22 Power consumption kW 1 3 2 4 5 Voltage frequency 230V 50Hz 230V 50Hz 230V 50Hz Noise level dB 45 60 65 Duct size working air mm D100 D125 D125 Duct size dry air mm D100 D125 D125 Supply d...

Page 22: ...EN IN REGEN IN AIR IN AIR IN REGEN OUT REGEN OUT 8 OVERALL AND MOUNTING DIMENSIONS DanVex AD 200 678 395 80 210 80 300 155 125 8 0 125 235 210 110 310 604 424 652 140 175 140 480 1 0 0 1 0 0 157 140 2...

Page 23: ...22 www danvex fi 870 571 245 240 205 650 100 100 1 2 5 1 2 5 145 650 190 200 420 505 DanVex AD 550 AIR OUT AIR IN REGEN IN REGEN OUT...

Page 24: ...ECTION DIAGRAM DanVex AD 200 Process motor Gear motor Humidistat Plug Humidity sensor Rocker Switch Heater Regen motor 230V 16A RVV3 x 1 5 mm 2 x 3m AC230V 50Hz Control Panel FY 2010 JS M3 M1 M2 MAN A...

Page 25: ...minals for Humidity limit signal Humidistat Plug Humidity sensor Rocker Switch Communication terminals Heater Regen motor DanVex AD 400 230V 16A RVV3 x 1 5 mm 2 x 3m AC230V 50Hz Control Panel RVV2 x 0...

Page 26: ...er Reserved terminals for Humidity limit signal Humidistat Plug Heater Rocker Switch Communication terminals Humidity sensor DanVex AD 550 AC230V 50Hz 3 x 4 mm 2 x 3m Control Panel RVV2 x 0 5 mm 2 x 1...

Reviews: