The following SW information can be viewed in the INFO LINE in the installer menu.
H101* = SW in Main control which is placed in the ventilation unit
C101* = SW in the control panel (HCP4)
F101*= SW in the remote control (HRC 2)
A101*= SW in the accessory control (HAC 1)
* SW examples
.
AUTO setting
In AUTO menu you can select the desired AUTO programs. (A1..)
RH% Set point
In AUTO menu, the RH% setpoint for demand-control can be set. The RH% setpoint be-
longs to the selected AUTO program No.
Warning:
If the RH% setpoint is set too low it may result in inconvenience for the occupants of the
house and materials in the house may dry up. Likewise a too high setpoint may result in
damp and mould in the building structure and the furniture.
Follow this procedure to change the RH set point:
Step
Action
1
Press RIGHT for 10 sec., till the installer menu is activated (ventilation
unit icon is flashing)
2
Press CENTER, previous AUTO program flashes
3
Press CENTER, previous RH% set point flashes
4
Press UP/DOWN in order to adjust RH% set point
5
Press CENTER to confirm the new set point and close
6
Press RIGHT for 10 sec. till the installer menu closes. (Ventilation unit
icon stops flashing)