53
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Appendix
: Technical data
en
Specification
Abbr .
Unit
HCV 300
HCV 500
HCV 700
Operating range (min. @ 50Pa -
max. @ 100Pa)
V
m3/h
50 to 180
80 to 300
80 to 450
Reference flow (@ 50Pa)
V
REF
m3/h
126
210
315
Performance
Temperature efficiency in accor-
dance with EN13141-7
h
SUP
%
from 85%
to 86%
from 85%
to 88%
from 85%
to 88%
Specific power consumption in
accordance with EN13141-7
SEL/SPI
m3/h
0.28
0.21
0.22
Leakage (external and internal)
in accordance with EN13141-7
-
%
< 2 (Class A1)
Filters in accordance with
ISO16890 / EN779
-
-
ISO Coarse 75% / G4
(optional: ePM1 55% / F7)
Ambient temperature for instal-
lation
t
SURR
°C
from +12 to +50
Outdoor temperature without
pre-heater installed
t
ODA
°C
from -12 to +50
Outdoor temperature with pre-
heater installed
t
ODA
°C
from -25 to +50
Maximum absolute humidity of
extract air
x
g/kg
10
Cabinet:
Exterior dimensions without wall
brackets)
W x H x D
mm
600 x 1000
x 430
700 x 1050
x 603
700 x 1050
x 750
Spigots/duct connections
Ø
mm
125 - fe-
male
160 - fe-
male
200 - fe-
male
Weight
m
kg
36
49.5
70
Heat conductivity of the
polystyrene insulation
l
W/(mK)
0.031
Heat transition figures -
polystyrene insulation
U
W/(m
2
K)
< 1
Fire class - polystyrene insulation
-
-
DIN 4102-1 Class B2
EN 13501 Class E
Drainage hose
Ø/length
" / m
3/4” – 1 m
Cabinet colour
RAL
-
9016
Electrical
Voltage
U
V
230
Max. power consumption (with-
out/with preheater)
P
W
170/870
170/1370
234/1834
Frequency
f
Hz
50
IP class
-
-
21
* The use of the preheating coil is recommended at outdoor temperatures below -3°C to
ensure balanced operation
Data sheet
HCV 300/500/700