INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Appendix
: Technical data
Specification
Abbr .
Unit
HCV 460 P2
Max. flow at 100Pa
V
100Pa
m3/h
460
Max. rated flow at 100Pa
V
max nom.
m3/h
360
Operating range DIBt
V
DIBt
m3/h
70 - 360
Working range Passivhaus at 100Pa
V
PHI
m3/h
106 - 270
EN 13141-7 reference flow @50Pa
V
REF
m3/h
252
Performance
Temperature efficiency in accordance
with EN13141-7l
h
SUP
%
86
Filters in accordance with EN779: 2012
class
-
G4/G4 (F7 optional)
Filters in accordance with ISO 16890
class
-
ISO Coarse (epM1 > 50%
optional)
Ambient temperature for installation
t
SURR
°C
from +12 to +40
Outdoor temperature range without
installed preheater
t
ODA
°C
from -12 to +50
Outdoor temperature with pre-heater
installed
t
ODA
°C
from -25 to +50
Maximum absolute humidity
of extract air
x
g/kg
10
Cabinet:
Dimensions (without brackets)
W x H x D
mm
540 x 1050x549 **
Spigots/duct connections
Ø
mm
Ø160 - female
Weight
m
kg
40
Thermal conductivity -
polystyrene insulation
l
W/(mK)
0.031
Heat transfer coefficient -
polystyrene insulation
U
W/(m
2
K)
U<1
Fire class - polystyrene insulation
-
-
DIN 4102 Class B2
EN 13501 Class E
Leakage (outside and inside) in
accordance with EN 13141-7
< 2 % (Class A1)
Drainage hose
Ø/length
" / m
3/4” - 2 m
Cabinet colour
RAL
-
9016
Electrical
Voltage
U
V
230
Max. power consumption
(without/with preheater)
P
W
230/2080
Frequency
f
Hz
50
IP class
class
-
21
* The use of the preheating coil is recommended at outdoor temperatures below -3°C to
ensure balanced operation
** +20mm fitting
Data sheet
HCV 460