INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care
: Error list
en
A B C
Error
code
Error
Possible cause
Action
required
Reset
16 R
2
E16
Firmware 2.9 and
up:
FPC fault (option)
Only active if the
"Fire Protection
Controller" acces-
sory is connected
to the unit.
No communica-
tion with the
fire protection
controller
Perform a
manual reset
by pressing the
alarm button on
the membrane
panel or by
turning the unit
off/on
Fire protection
controller with
this address has
previously been
installed but can
no longer be
reached
Check connection
to fire protection
controller
There is no posi-
tion feedback for
fire dampers
A fire damper
is closed, but
should be open
Check power supply
to fire dampers
Check fire dampers
internal fire detector
Error in monthly,
weekly or manual
test of fire damp-
ers
Fire damper stuck
in either open or
closed position
The fire damper is
blocked.
Fire dampers are con-
nected incorrectly
Fire damper defec-
tive