69
060
78
3 •
V
ersi
on
1.
3 •
26
.04
.2
011
Technical data,
continued
Electrical data
The table shows the technical electrical data for HCV 3 and HCV 5.
Specification
Unit
HCV 3
HCV 5
Integrated control panel HCP 4 in
front cover
- Yes
Supply voltage
1x230 V, 50 Hz
Max. current consumption, w/o pre-
heat and afterheat
A 0,4 0,7
Max. power consumption, w/o pre-
heat and afterheat
W 88 154
Cabinet, sound
data
The table shows the technical sound data for HCV 3 and HCV 5.
Specification
Unit
HCV 3
HCV 5
m
3
/h 140
220
External pressure
Pa
70
100
70
100
Sound power level, cabinet
Lw dB(A)
51
53
54
56
Sound pressure, cabinet at 1 metre
3
Lp dB(A)
47
49
50
52
Duct, sound data
The table shows the technical sound data for HCV 3 and HCV 5.
Specification
unit
HCV 3
HCV 5
63 Hz (supply/extract)
Lw dB(A)
34/35
36/37 37/38 38/39
125 Hz (supply/extract)
Lw dB(A)
40/38
42/40 42/41 44/43
250 Hz (supply/extract)
Lw dB(A)
43/40
45/43 53/50 55/52
500 Hz (supply/extract)
Lw dB(A)
44/44
47/47 42/42 45/45
1000 Hz (supply/extract)
Lw dB(A)
36/41
38/43 41/36 43/38
2000 Hz (supply/extract)
Lw dB(A)
27/33
29/33 39/34 40/35
4000 Hz (supply/extract)
Lw dB(A)
19/24
21/26 27/20 29/22
Sound power level, supply air duct
Lw dB(A)
57
59
57
59
Sound power level, extract air duct
Lw dB(A)
56
58
56
58
Sound pressure, supply air duct,
1 metre
2
Lp dB(A)
43
45
43
45
Sound pressure, extract air duct,
1 metre
2
Lp dB(A)
42
44
42
44
3
Measured in a hard room of approx. 10 m
2
, with 2,5 metres to ceiling and medium absorption.
2
Measured at 1 metre distance in free area.
2
Measured at 1 metre distance in free area.
Summary of Contents for HCV 3
Page 2: ...2005 layout...
Page 34: ...32 Dimensioner HCV 3 Aggregatets di mensioner Illustrationen viser dimensionerne p en HCV 3...
Page 38: ...36 Appendiks A Ydelse og specifik ventilatoreffekt HCV 3 Forts ttes p n ste side...
Page 40: ...38 Appendiks A Ydelse og specifik ventilatoreffekt fortsat HCV 5 Forts ttes p n ste side...
Page 72: ...70 Dimensions HCV 3 Dimensions of the unit The illustration shows the dimensions of the HCV 3...
Page 76: ...74 Appendix A Performance and specific fan effect HCV 3 Continued overleaf...
Page 78: ...76 Appendix A Performance and specific fan effect continued HCV 5 Continued overleaf...
Page 114: ...112 Abmessungen HCV 5 Abmessungen des Ger ts Die Abbildung zeigt die Abmessungen eines HCV 5...
Page 122: ......
Page 160: ...158 Annexe A Performances et effect ventilateur sp cifique HCV 3 Suite la page suivante...
Page 162: ...160 Annexe A Performances et effect ventilateur sp cifique suite HCV 5 Suite la page suivante...
Page 165: ...2005 layout...