Set points and control strategies,
continued
Frost protection,
continued
3) Recommendation
To secure a balanced air flow with out intentional shut-down, Dantherm Air Handling
A/S recommends installing pre-heat in areas where temperatures during longer peri-
ods of time is below ÷6 °C.
In areas where temperatures constantly are below ÷13 °C, installing pre-heat is a
must to secure optimal operation.