19
060804
•
Ve
rs
ion
1.6
•
22.01.2
01
9
en
Preventive maintenance,
continued
Drip tray
Make sure that the condensate drain is not clogged in the drip tray and clean the drip
tray with soapy water and a brush or a cloth every second year to ensure good hygiene
inside the unit.
Internal cleaning
The unit must be kept clean to ensure error free operation and good hygiene.
Internal cleaning are only necessary if the unit is open e.g. in connection with service.
Check the internal surface in the unit. If it is dirty, clean with a wet cloth, brush, vacuum
cleaner or the like.
Drain, external con-
nection and duct
flow
Drain, external connections and hose installations must be checked once a year before
the risk of frost occurs.
Make sure that the hose is firmly connected to the unit and that the water trap is filled
with water.
Make sure that the hose is not broken and that the hose drops minimum 1% toward the
drain, and that the hose is protected against frost from unit to drain.
Heat exchanger
Check the heat exchanger for dirt every second year.
Clean the heat exchanger with a soft brush and a vacuum cleaner at all four inlets,
In special cases, e.g. if there are clear traces of accumulated, dirty condensate water in
the heat exchanger, it is necessary to remove the heat exchanger from the unit and
clean the exchanger with soapy water.
Controller
The controller must only be checked if an error occurs on the unit.
Make sure that all connections are all right and that the controller is clean and free with
out dust or moisture.
Service intervals
The below table gives an overview of the service intervals for the different parts.
Part
Function
Service interval
1
Filter
Twice a year
2
External drain
Once a year
3
Heat exchanger
Every second year
4
Fans
Every second year
5
Drip tray/internal drain
Every second year
6
Internal air channels
Every second year
7
Bypass module
Every second year
8
Controller
Only when errors occurs
Continued overleaf
Summary of Contents for HCH 5
Page 1: ...HCH 5 HCH 8 Installation and Service manual Rev 1 6 en da de fr ...
Page 42: ...8 Fortsættes på næste side 1000 mm 1500 mm 100 mm Min 50 mm komprimeret isolering ...
Page 74: ...8 Fortsetzung nächste Seite 100 mm 1000 mm 1500 mm Min 50 mm komprimierte Isolierung ...
Page 101: ...35 060804 Version 1 6 22 01 2019 DA de ...
Page 102: ...36 ...
Page 139: ...1 074913 Version 1 0 02 10 2012 ...