background image

46310-IG-0300 <90-00226>

 P

AGE

 7

6.

Select View in the toolbar. Then select Options. Verify that the
module part number shown is appropriate for the Dantel alarm
unit being installed. Select the module part number to match that
shown on the front inside plate of the Dantel unit.

7.

Set the TL1 Issue to Issue 5.

8.

Set the Respond to Invalid SID to Yes (default setting)

9.

Select Transfer in the toolbar. Then select Download.

10.

Verify the download parameters and enter the PointMaster pass-
word. Normal parameters are:

9600 baud

8-bit word length

No parity

1 stop bit

Full duplex

Timeout 3 seconds

Resend 3

Transfer mode direct

PointMaster address 1

11.

Select the Transfer button on the bottom of the screen. Watch for
“Download Complete”.

12.

End of section 3. Continue on to section 4.

S

ECTION

 4 - F

INAL

 S

TEPS

Upon completion of the download, disconnect the PC from the
PointMaster’s Craft Port and do a soft reboot. Before calling into
NOC, wait 5 minutes for the PointMaster to go through its self-
test.

1.

Create some Major Alarms on the PointMaster to simulate actual
alarm conditions and verify that these alarms are seen on NOC
terminals. They should match the alarm designations on the equip-
ment.

2.

The remaining alarms shall be verified by strapping to ground and
touching the pins on the Dantel Pointmaster.

3.

Clear all alarms. If the Craft Port is wired for remote access, the
NOC operator should verify that they can enter the menu to make
configuration changes remotely.

4.

This completes the Installation Guide.

INSTALLATION

Summary of Contents for PointMaster TL1

Page 1: ...or store circuit boards near strong electrostatic electromag netic magnetic or radioactive fields For more complete information on electrostatic discharge safety precautions refer to BellcoreTM Techni...

Page 2: ...t the proper interface cable is on site If the TL1 Editor is already loaded on your computer skip Section 1 and begin at Section 2 SECTION 1 LOAD TL1 POINTMASTER EDITOR For this section refer to the T...

Page 3: ...ge safety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Power Supply Card 1 On the Power Supply Module set strap J7 across pins 1 and 2 2 On the RS 232 subassembly located on the P...

Page 4: ...he front of the Dantel unit 1 Open the TL1 Editor program installed in section 1 2 From the command line select File then Terminal 3 From the command line select Port then select Communica tions Confi...

Page 5: ...the TL1 PointMaster practice 8 Check if any cards failed the diagnostics test and replace as needed Where no cards failed but a flashing red LED persists contact Dantel Contact proper supply personnel...

Page 6: ...ion 3 and press Enter Screen moves to line 4 3 Set Date 25 Enter the date MM DD YYYY 26 If a password is desired select option 4 and press Enter Screen moves to line 4 4 Set Password 27 Enter your pas...

Page 7: ...ansfer button on the bottom of the screen Watch for Download Complete 12 End of section 3 Continue on to section 4 SECTION 4 FINAL STEPS Upon completion of the download disconnect the PC from the Poin...

Page 8: ...en instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respec...

Reviews: