Select View in the toolbar. Then select Options. Verify that the
module part number shown is appropriate for the Dantel alarm
unit being installed. Select the module part number to match that
shown on the front inside plate of the Dantel unit.
7.
Set the TL1 Issue to Issue 5.
8.
Set the Respond to Invalid SID to Yes (default setting)
9.
Select Transfer in the toolbar. Then select Download.
10.
Verify the download parameters and enter the PointMaster pass-
word. Normal parameters are:
♦
9600 baud
♦
8-bit word length
♦
No parity
♦
1 stop bit
♦
Full duplex
♦
Timeout 3 seconds
♦
Resend 3
♦
Transfer mode direct
♦
PointMaster address 1
11.
Select the Transfer button on the bottom of the screen. Watch for
“Download Complete”.
12.
End of section 3. Continue on to section 4.
S
ECTION
4 - F
INAL
S
TEPS
Upon completion of the download, disconnect the PC from the
PointMaster’s Craft Port and do a soft reboot. Before calling into
NOC, wait 5 minutes for the PointMaster to go through its self-
test.
1.
Create some Major Alarms on the PointMaster to simulate actual
alarm conditions and verify that these alarms are seen on NOC
terminals. They should match the alarm designations on the equip-
ment.
2.
The remaining alarms shall be verified by strapping to ground and
touching the pins on the Dantel Pointmaster.
3.
Clear all alarms. If the Craft Port is wired for remote access, the
NOC operator should verify that they can enter the menu to make
configuration changes remotely.
4.
This completes the Installation Guide.