P
AGE
4
46310-IG-0300 <90-00226>
8.
Install all fuses and power the unit up using a white color, GMT-
type, 1 1/3 amp fuse.
9.
Power connections complete. Continue with status check.
Status Check
Refer to the LED’s portion of the Circuit Description section
of the TL1 PointMaster practice.
10.
Check the status of the CPU/Alarm LED.
♦
Solid Green - normal CPU operation
♦
Solid Red - actual alarm on one or more points
♦
Flashing Red - card failure
Continue to following steps.
11.
Verify that the fuse LED is off.
12.
Verify that the low battery LED is off.
13.
End of section 2. Continue on to section 3.
S
ECTION
3 - D
ATABASE
C
ONFIGURATION
Using a straight-through cable, connect the PC or laptop’s
communications port (DB-9) to the Craft Port (DB-9) on the
front of the Dantel unit.
1.
Open the TL1 Editor program installed in section 1.
2.
From the command line, select File, then Terminal.
3.
From the command line, select Port, then select Communica-
tions. Confirm that the port is set for:
♦
9600 baud
♦
8-bit word length
♦
No parity
♦
1 stop bit
♦
full duplex
Click OK.
4.
Reselect Port from the command line. Select Connect.
NOTE:
Read all of step 5 before any of the functions described in
step 5.
5.
Perform a hard reset of the Dantel unit by pressing the reset but-
ton and holding it for 10 seconds. Watch for the diagnostic results
on the screen. After power up or reset, the PointMaster performs a
self-test, after which it reports the results of that test and prompts
you to enter “!!!” to keep the connection.
N
OTE
:
For additional informa-
tion on configuration of
the PointMaster, refer to
the Configuration por-
tion of the Installation
section of the TL1 Point-
Master practice.
INSTALLATION
CONTINUED
. . .