8.

Install all fuses and power the unit up using a white color, GMT-
type, 1 1/3 amp fuse.

9.

Power connections complete. Continue with status check.

Status Check

Refer to the LED’s portion of the Circuit Description section
of the TL1 PointMaster practice.

10.

Check the status of the CPU/Alarm LED.

Solid Green - normal CPU operation

Solid Red - actual alarm on one or more points

Flashing Red - card failure

Continue to following steps.

11.

Verify that the fuse LED is off.

12.

Verify that the low battery LED is off.

13.

End of section 2. Continue on to section 3.

S

ECTION

 3 - D

ATABASE

 C

ONFIGURATION

Using a straight-through cable, connect the PC or laptop’s
communications port (DB-9) to the Craft Port (DB-9) on the
front of the Dantel unit.

1.

Open the TL1 Editor program installed in section 1.

2.

From the command line, select File, then Terminal.

3.

From the command line, select Port, then select Communica-
tions
. Confirm that the port is set for:

9600 baud

8-bit word length

No parity

1 stop bit

full duplex

Click OK.

4.

Reselect Port from the command line. Select Connect.

NOTE:

Read all of step 5 before any of the functions described in
step 5.

5.

Perform a hard reset of the Dantel unit by pressing the reset but-
ton and holding it for 10 seconds. Watch for the diagnostic results
on the screen. After power up or reset, the PointMaster performs a
self-test, after which it reports the results of that test and prompts
you to enter “!!!” to keep the connection.

N

OTE

:

For additional informa-
tion on configuration of
the PointMaster, refer to
the Configuration por-
tion of the Installation
section of the TL1 Point-
Master practice.

INSTALLATION

CONTINUED

 . . .

Summary of Contents for PointMaster TL1

Page 1: ...or store circuit boards near strong electrostatic electromag netic magnetic or radioactive fields For more complete information on electrostatic discharge safety precautions refer to BellcoreTM Techni...

Page 2: ...t the proper interface cable is on site If the TL1 Editor is already loaded on your computer skip Section 1 and begin at Section 2 SECTION 1 LOAD TL1 POINTMASTER EDITOR For this section refer to the T...

Page 3: ...ge safety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Power Supply Card 1 On the Power Supply Module set strap J7 across pins 1 and 2 2 On the RS 232 subassembly located on the P...

Page 4: ...he front of the Dantel unit 1 Open the TL1 Editor program installed in section 1 2 From the command line select File then Terminal 3 From the command line select Port then select Communica tions Confi...

Page 5: ...the TL1 PointMaster practice 8 Check if any cards failed the diagnostics test and replace as needed Where no cards failed but a flashing red LED persists contact Dantel Contact proper supply personnel...

Page 6: ...ion 3 and press Enter Screen moves to line 4 3 Set Date 25 Enter the date MM DD YYYY 26 If a password is desired select option 4 and press Enter Screen moves to line 4 4 Set Password 27 Enter your pas...

Page 7: ...ansfer button on the bottom of the screen Watch for Download Complete 12 End of section 3 Continue on to section 4 SECTION 4 FINAL STEPS Upon completion of the download disconnect the PC from the Poin...

Page 8: ...en instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respec...

Reviews: