P
AGE
60
46210/46220-0998 <90-00036>
Remarks:
After SG, # can be a range of subgroups from 1 through 16 or the
word ALL. Here are examples:
SG 4
Alarm subgroup 4 (alarm points 49-64)
SG -10
Alarm subgroups 1-10 (alarm points 1-160)
SG 10-
Alarm subgroups 10-16
SG 5-10
Alarm subgroups 5-10
SG ALL
All alarms
After REVERSE, # can be a range of points from 1 through 16.
See the examples above.
Input Example:
>SG 1 REVERSE
Output Response
SG INPUT REVERSE
SG 1 REVERSES . . . . . . . . . . . . .
Input Example:
>SG 9 REVERSE 9
This example would reverse the condition for reporting an alarm
on input 137 (input 9 of subgroup 9).
Output Response:
A change of status report is issued (see OUTPUT MESSAGES).
REVISION
Purpose:
Gives the revision level of the 46210/46220’s firmware.
Format:
REVLIST
PRINTER SYNTAX