If one of the alarm interface boards inside the unit is removed or
disconnected, a point-64 alarm failure is generated in the alarm
display reporting that board’s alarms.
Connect a dumb terminal or personal computer operating as a
dumb terminal to the master port for maintenance purposes.
Refer to the Printer Syntax chapter.
To replace the fuse:
1.
Open the 46210/46220 (refer to Fig. 20).
2.
Pull the power supply and CPU boards down from the other cir-
cuitry (refer to Fig. 21).
3.
Replace the fuse (F1) on the power supply board with a GMT-type
fuse rated at one ampere (refer to Fig. 22).
4.
Push the power supply and CPU boards back into place and close
the unit.
5.
Fuse replacement complete.