If you do not connect a Status Monitor or GPP to the MAP
master port, set S5-2 UP.
Switch S5-3
♦
If you connect a Status Monitor or GPP to the MAP printer
port, set switches S5-3 DOWN and S2-7 UP.
♦
If you do not connect a Status Monitor or GPP to the MAP
printer port, set S5-3 UP.
Switch S5-4
Always leave switch S5-4 UP.
Switch S5-5
♦
Report level D alarms to the printer port by setting switch
S5-5 UP.
♦
Treat level D alarms as status points (that is, the MAP ig-
nores the alarms) by setting switch S5-5 DOWN.
Switch S5-6
Enable extended addressing by setting switch S5-6 DOWN. Set
extended addressing with switches S6 and S7.
Switch S5-7
The MAP has battery-backed memory which prevents loss of the
system configuration in a power outage. When power comes
back on, set MAP operation using switch S5-7:
♦
Have the MAP resume operation where it left off (if the
memory is intact) by setting switch S5-7 DOWN.
♦
Have the MAP erase memory and restart operation by set-
ting switch S5-7 UP.
Switch S5-8
When you use DCM protocol on the data port, set the data port
data rate using switch S5-8:
♦
Set switch S5-8 UP for a 1200 baud data rate.
♦
Set switch S5-8 DOWN for a 9600 baud data rate.
S
WITCH
S6 & S7 - E
XTENDED
A
DDRESSING
This switch allows you to enable extended addressing. Refer to
Table H for switch settings. When S5-6 is in the DOWN position
(enabling extended addressing):
♦
S6 sets the Master Port address
♦
S7 sets the Printer Port address
SWITCH SETTINGS