46020-38-0299 <90-00029>
P
AGE
27
If the MAP interfaces an E-System Adapter, set the
E-System mode to ON when you use the MAP as #1 or #3.
Set the E-System mode OFF when you use the MAP as #2
or #4 or when the MAP interfaces to another MAP or
computer.
♦
Set the MAP printer port ID address using switches S4-7 and
S4-8.
You can set the address from 1 to 255. You can set the
address from 1 to 4 when the MAP interfaces an
E-System Adapter.
The master port data rate is 1200 baud. You do not have to set
any switches.
TBOS/Printer Protocol
♦
Set the number of master port displays using switches S4-1
to S4-3. Refer to Table F.
♦
Switch S4-4 is not used. Leave in the OFF position.
♦
Set the master port baud rate using switches S4-5 and S4-6.
Master port baud rates are 1200 and 2400 baud.
♦
Set the printer port baud rate using switches S4-7 and S4-8.
Printer port baud rates are 300, 1200, 2400 and 9600
baud.
TBOS/TBOS Protocol
♦
Set the number of master port displays using switches S4-1
to S4-3. Refer to Table G.
♦
Switch S4-4 is not used. Leave in the OFF position.
♦
Set the master port baud rate using switches S4-5 and S4-6.
Master port baud rates are 1200 and 2400 baud.
♦
Set the printer port baud rate using switches S4-7 and S4-8.
Printer port baud rates are 300, 1200, 2400 and 9600
baud.