M-AI-VT-001-EN Rev.C.1
Overview of the VTT Compressor
Drive Module Technical
Specifications
Model
N165
N232
N262
Nominal Power output (kW)
165
232
262
Mains Input AC Current
FLA
380 V
271
380
405
400 V
235
330
378
460 V
-
-
333
575 V
188
264
TBD
LRA
380 V
271
380
419
400 V
235
330
416
460 V
-
-
366
575 V
TBD
TBD
TBD
Maximum Output Current
380 V
318
424
438
400 V
318
424
406
460 V
263
350
395
575 V
TBD
TBD
TBD
Minimum Motor Cable Sizes
Recommended Cable Type
Flexible Locomotive (Stranded) Copper
Recommended Cable size, mcm (AWG)
2x3/0 per phase
2x4/0 per phase
Recommended Ground cable size, (AWG )
#2
#2
Max external mains AC fuses (A)
380 V, 400 V and 460 V
400
550
630
575 V
TBD
TBD
Table 3
Electrical Data
Electronic Control System
The control system architecture consists of three
electronic boards:
• Compressor Control Module (CCM)
• Pulse Width Modulator (PWM)
• Compressor Interface Module (CIM)
The CCM is the center point for all electronics
in the compressor and communicates with
the PWM board, CIM board, and Drive Module.
Communication between the compressor and
chiller controller is accessed through the CIM.
NOTE
The minimum motor cable sizes listed are for factory full load current. Cable sizes for any amperage setting
below the factory settings should be sized according to local standards using the flexible locomotive
copper cable.
• 2 cables per phase, 6 total from the drive to
the motor.
• Using two cables run each of the three phases
through each conduit.
Phase cable
• Flexible locomotive (stranded) copper cable
• Cables should be shielded or Screened
• See Table 3 for sizing
• Cables should be shielded or Screened
Ground cable
•
#1 AWG copper cable
Motor Cable Sizing
NOTE
It is recommended to keep the motor cable length as short as possible, preferably not to exceed 5 m (15’).