VLT
®
2800 Series
Programming
DC link voltage, parameter 525:
Gives the intermediate circuit voltage in the
frequency converter.
Thermal load, motor [%], parameter 526:
Gives the calculated/estimated thermal load on
the motor. 100% is the cut-out limit. See also
parameter 128
Thermal motor protection
.
Thermal load INV [%], parameter 527:
Gives the calculated/estimated thermal load on the
frequency converter. 100% is the cut-out limit.
Digital input, parameter 528:
Gives the signal status from the 5 digital inputs (18, 19,
27, 29 and 33). Input 18 corresponds to the bit on the
extreme left.
’
0
’
= no signal,
’
1
’
= connected signal.
Terminal 53 analogue input [V], parameter 529:
Gives the voltage value for the signal on terminal 53.
Terminal 60 analogue input [mA], parameter 531:
Gives the present value for the signal on terminal 60.
Pulse reference [Hz], parameter 532:
Gives a pulse frequency in Hz connected to terminal 33.
External reference, parameter 533:
Gives the sum of external references as a percentage
(sum of analogue/pulse/serial communication)
in the range from Minimum reference, Ref
MIN
to Maximum reference, Ref
MAX
.
Status word, parameter 534:
Gives the present status word for the frequency
converter in Hex. See
Serial communication
for the VLT 2800.
Bus feedback 1, parameter 535:
Allows writing of a bus feedback value which will
then form part of the feedback handling.
Inverter temperature, parameter 537:
Gives the present inverter temperature on the
frequency converter. The cut-out limit is 90-100
°C, with cut back in at 70 ± 5 °C.
Alarm word, parameter 538:
Gives in Hex code which alarm is on the
frequency converter. See
Warning word, extended
status word and alarm word.
Control word, parameter 539:
Gives the present control word on the frequency
converter in Hex. See
Serial communication
for the VLT 2800.
Warning word, parameter 540:
States whether there is a warning on the frequency
converter in Hex. See
Warning word, extended
status word and alarm word.
Extended status word, parameter 541:
States whether there is a warning on the frequency
converter in Hex code. See
Warning word,
extended status word and alarm word.
Pulse count, parameter 544:
This parameter can be read out via the LCP display
(009-012). When you run with counter stop, this
parameter enables you, either with or without reset, to
read the number of pulses registered by the device.
The highest frequency is 67.6 kHz, while the lowest is 5
Hz. The counter is reset when counter stop is restarted.
560 N2 Override release time
(N2 OVER.REL.TIME)
Value:
1 - 65534 (OFF) sec.
✭
OFF
Function:
In this parameter, the maximum time is set which is
expected to pass between the receipt of two N2
telegrams in a row. If this time is exceeded, the serial
communication is assumed to have stopped and all
points in the N2 point-map which are overridden
will be released in the order below:
1.
Release Analog Outputs from point
address (NPA) 0 to 255.
2.
Release Binary Outputs from point
address (NPA) 0 to 255.
3.
Release Internal Floating Points from point
address (NPA) 0 to 255.
4.
Release Internal Integer Points from point
address (NPA) 0 to 255.
5.
Release Internal Byte points from point
address (NPA) 0 to 255.
Description of choice:
Set the required time.
561 Protocol
(PROTOCOL)
Value:
✭
FC protocol (FC PROTOKOL)
[0]
Metasys N2 (METASYS N2)
[1]
Modbus RTU
[3]
Function:
There is a choice of three different protocols.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
125