![Danfoss VT2800 Series Design Manual Download Page 118](http://html1.mh-extra.com/html/danfoss/vt2800-series/vt2800-series_design-manual_507920118.webp)
VLT
®
2800 Series
Output frequency has the following format:
0-16384 (4000 Hex)
0-100% (Par. 201
Output frequency low limit
- Par. 202
Output
frequency high limit
).
Example - Status word and current output frequency:
The master receives a status message from the
frequency converter that the current output frequency
is 50% of the output frequency range.
Par. 201
Output frequency low limit
= 0 Hz
Par. 202
Output frequency high limit
= 50 Hz
Status word = 0F03 Hex.
Output frequency = 2000 Hex
⇒
50% of the
frequency range, corresponding to 25 Hz.
MG.28.E9.02 - VLT is a registered Danfoss trademark
118