1.
Procedure
Set
parameter 1-1 Command Source
to Network for the soft starter to accept commands from the EtherNet/IP Card.
4.5 On-board Web Server
4.5.1 Connect to the Device
To configure settings using the on-board web server, the EtherNet/IP Card must be installed in a soft starter, control power must be
available, and the card and computer must both be connected to the Ethernet network.
The computer must use a fixed IP address (not DHCP) and the same subnet mask as the card. The default IP address for the card is
192.168.0.2. The default subnet mask is 255.255.255.0.
e7
7h
a8
07
.1
0
Once connected, the web server reports basic information about the card and the soft starter.
MCD 600
e7
7h
a8
12
.1
0
AN353423548483en-000101 / 130R0945
10 | Danfoss A/S © 2020.12
Device Configuration
EtherNet/IP Card
Installation Guide