4 Installation

4.1 Mounting

Procedure

1.

Make sure that the power to the drive is disconnected.

2.

Remove the front cover from the drive.

3.

Remove the LCP (Local Control Panel) or blind cover, and then remove the LCP cradle from the drive.

4.

Disconnect the communication cables from the existing MCA option card.

5.

Remove the existing MCA option card from the drive.

6.

Fit the new VLT® PROFINET MCA 120 option card into slot A. Mount the option with the Ethernet port facing up for top cable entry.

7.

Connect the Ethernet cables. See 

illustration 1

 and 

table 4

 for the definition of PROFINET connectors.

e

3

0

b

d

9

1

0

.1

0

2

4

3

M12 PIN#

RJ45

8

1

1

.   .   .   .   .   .  

Illustration 1:  PROFINET Connectors

Table 4: PROFINET Connectors

Signal

M12 PIN#

RJ 45

RX +

1

1

TX +

2

2

RX -

3

3

TX -

4

4

8.

Set the address switches if needed.

9.

Fit the LCP cradle.

10.

Fit the LCP or blind cover in the LCP cradle.

11.

Fit the front cover on the drive.

12.

Connect power to the drive.

4.2 Setting Address Switches

The option has address switches that are used to set the station name (host name).

When all switches are set to ON, or all are set to OFF, change the station name via 12-08 Host Name or via DCP command.

In all other combinations, the address switches have priority over the parameter setting. The station name is set based on the value

in 15-40 FC Type, and a 3-digit number selected from the DIP settings.

Installation

Installation Guide  | VLT® PROFINET MCA 120

AN274237376992en-000101 / 130R0856 | 5

Danfoss A/S © 2019.03

Summary of Contents for VLT PROFINET MCA 120

Page 1: ...omationDrive FC 361 The installation guide is intended for use by qualified personnel Users are assumed to be familiar with the VLT drive with PROFINET technology and with the PC or PLC used as a mast...

Page 2: ...pe motors and remote DC link supplies including battery back ups UPS and DC link connections to other drives Wait for the capacitors to discharge fully The minimum waiting time is specified in table D...

Page 3: ...ments and exterior underground laying natural and synthetic oil grease coolants lubricants chemicals high and low temperatures UV radiation and so on Table 2 Cable Specifications for Application Types...

Page 4: ...Delay skew 20 ns 100 m Transfer impedance 50 m m at 10 MHz Technical Data Installation Guide VLT PROFINET MCA 120 AN274237376992en 000101 130R0856 4 Danfoss A S 2019 03...

Page 5: ...1 1 Illustration 1 PROFINET Connectors Table 4 PROFINET Connectors Signal M12 PIN RJ 45 RX 1 1 TX 2 2 RX 3 3 TX 4 4 8 Set the address switches if needed 9 Fit the LCP cradle 10 Fit the LCP or blind co...

Page 6: ...st Names Setting Switch 8 7 6 5 4 3 2 1 12 08 Host Name 128 64 32 16 8 4 2 1 005 OFF OFF OFF OFF OFF ON OFF ON 035 OFF OFF ON OFF OFF OFF ON ON 082 OFF ON OFF ON OFF OFF ON OFF 212 ON ON OFF ON OFF ON...

Page 7: ...ustration 3 Wiring 2 Fix the cable to the metal base plate using the springs 3 Tie down the cable and route it with other control wires inside the unit NOTICE Do not strip the Ethernet cable Ground th...

Page 8: ...erations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss log...

Reviews: