Parameters
130BE205.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
4 - 20mA
+
-
FC
+24 V
Function
Setting
Parameter 6-12
Terminal 53 Low
Current
4 mA*
Parameter 6-13
Terminal 53
High Current
20 mA*
Parameter 6-14
Terminal 53 Low
Ref./Feedb.
Value
0
Parameter 6-15
Terminal 53
High Ref./Feedb.
Value
50
Parameter 6-19
Terminal 53
mode
[0] current
*=Default value
Notes/comments:
Table 7.3 Analog Speed Reference (Current)
Parameters
130BE208.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
≈ 5kΩ
FC
+24 V
Function
Setting
Parameter 6-10
Terminal 53 Low
Voltage
0.07 V*
Parameter 6-11
Terminal 53
High Voltage
10 V*
Parameter 6-14
Terminal 53 Low
Ref./Feedb.
Value
0
Parameter 6-15
Terminal 53
High Ref./Feedb.
Value
50
Parameter 6-19
Terminal 53
mode
[1] voltage
*=Default value
Notes/comments:
Table 7.4 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
130BE209.11
+24 V
Function
Setting
Parameter 5-10
Terminal 18
Digital Input
*[8] Start
Parameter 5-12
Terminal 27
Digital Input
[19] Freeze
Reference
Parameter 5-13
Terminal 29
Digital Input
[21] Speed
Up
Parameter 5-14
Terminal 32
Digital Input
[22] Slow
*=Default value
Notes/comments:
Table 7.5 Speed Up/Slow
Start (18)
Freeze ref (27)
Speed up (29 )
Speed down (32 )
Speed
Reference
130BB840.11
Figure 7.1 Speed Up/Slow
Application Examples
Instruction Manual
MG07A122
Danfoss A/S © 11/2015 All rights reserved.