8.2.2.3 Command Examples
Byte Value
Description
0
0b01000000 (64d, 0x40)
Command: Start the soft starter.
1
0b00000000 (00d, 0x00) or
0b00100000 (32d, 0x20)
Command: Select primary or secondary motor settings when starting.
0
0b10000000 (128d, 0x80)
Command: Reset the soft starter.
The reset only occurs when the previous reset bit is 0, otherwise the value of 1 is ig-
nored.
0
0b11000000 (192d, 0xC0)
Command: Reset and start the soft starter.
0
0bX0000000 (00d, 0x00)
Command: Stop the soft starter.
8.2.3 Status Information (Assembly Instance 154d)
To retrieve status data from the soft starter, use assembly class 04d (0x04), assembly instance 154d (0x9A), attribute 03d (0x03).
8.2.3.1 Bytes 0–1: Starter State
Bits
Function
Details
0
Ready
0 = Not ready
1 = Ready to start
1
Operating mode
0 = Program mode
1 = Operating mode
2
Running
0 = Not ready, ready to start, or tripped
1 = Starting, Running, Stopping, or Jogging
3
Trip
0 = Not tripped
1 = Tripped
4
Jog forward
1 = Jog forward
5
Jog reverse
1 = Jog reverse
6
Reserved
7
Warning
0 = No warning
1 = Warning
8
Ramping
1 = Running (full voltage at the motor)
9
Local/remote
0 = Hand on
1 = Auto on
10
Reserved
11
Reserved
12
Reserved
AN427641276310en-000101 / 175R1187
24 | Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide