ISD Flange
130BC458.10
Illustration 4.8 Hybrid Cable Connection for ISD Flange
IEC Flange
130BC459.10
Illustration 4.9 Hybrid Cable Connection for IEC Flange
4.3.1 Layout and Routing
Observe the following instructions for cable layout and
routing:
•
The total length of the cables in a system may
not exceed 100 m (maximum CAN bus length at
500 Kbit/s).
•
The cables should generally be routed to keep
the cable runs as short as possible.
•
Consult Danfoss if the length of the CAN bus
exceeds 100 m.
Routing in drag chains
The hybrid cable is compatible with drag chains and
therefore suitable for use in moving systems. The number
of bending cycles is strongly dependent on individual
conditions and must therefore be determined in advance
for each application.
4.3.2 Hybrid Cable
The ends of the connection cables are fitted with M23
connectors. The feed cable is pigtailed at the input end to
allow the individual wires to be connected to the
connection box.
Cable Design
CAN Lines
Power Cable
Rated voltage
600 V (due to
enclosure in a
common sheath with
power wires)
600 V
Test voltage
According to standard According to
standard
Load
<500 mA
Max. 10 A
continuous current
Number of wires
2 x 2 twisted pairs
4
Cross section
0.5 mm
2
1/2.5 mm
2
Characteristic
impedance of data
pair
80-200
Ω
–
Colour-coded wires Data pair: blue/white
Supply: red/black
PE: green/yellow
Phase: black with
printed numbers
(1, 2, 3)
Table 4.6 Cable Structure
Description
VLT
®
ISD 410 Servomotor Operating Instructions
MG75D102 - VLT
®
is a registered Danfoss trademark
17