1.2.5 Disposal Instruction
Equipment containing electrical components
must not be disposed of together with domestic
waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
1.3 Installation
1.3.1 Before Starting Repair Work
1.
Disconnect FC101 from mains (and external DC
supply, if present.)
2.
Wait as stated in the table below for discharge of
the DC-link:
Voltage (V)
Power range (kW)
Min. waiting time
(minutes)
3 x 200
0.25 – 3.7
4
3 x 200
5.5 – 45
15
3 x 400
0.37 – 7.5
4
3 x 400
11 – 90
15
3 x 600
2.2 – 7.5
4
3 x 600
11 – 90
15
3.
Remove motor cable
1.3.2 Side-by-Side Installation
The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
Power
Clearance above/
below (mm/inch)
Frame
IP class
3 x 200-240 V
3 x 380-480 V
3 x 525-600 V
H1
IP20
0.25-1.5 kW/0.33-2 Hp
0.37-1.5 kW/0.5-2 Hp
100/4
H2
IP20
2.2 kW/3 Hp
2.2-4 kW/3-5.4 Hp
100/4
H3
IP20
3.7 kW/5 Hp
5.5-7.5 kW/7.5-10 Hp
100/4
H4
IP20
5.5-7.5 kW/7.5-10 Hp
11-15 kW/15-20 Hp
100/4
H5
IP20
11 kW/15 Hp
18.5-22 kW/25-30 Hp
100/4
H6
IP20
15-18.5 Kw/20-25 Hp
30-45 kW/40-60 Hp
22-30 kW/30-40 Hp
200/7.9
H7
IP20
22-30 kW/30-40 Hp
55-75 kW/100-120 Hp
45-55ø W/60-100 Hp
200/7.9
H8
IP20
37-45 kW/50-60 Hp
90 kW/125 Hp
75-90 kW/120-125 Hp
225/8.9
H9
IP20
2.2-7.5 kW/3-10 Hp
100/4
H10
IP20
11-15 kW/15-20 Hp
200/7.9
NOTE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.