1.7.2 Mains Supply 3 x 380-480 V AC
Frequency
converter
PK37
PK75
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical
shaft
output
(kW)
0.37
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical
shaft
output
(hp)
0.5
1.0
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
70.0
100.0
125.0
IP20
frame
H1
H1
H1
H2
H2
H2
H3
H3
H4
H4
H5
H5
H6
H6
H6
H7
H7
H8
Max.
cable
size
in
terminals
(mains,
motor)
[mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
4/10
4/10
16/6
16/6
16/6
16/6
35/2
35/2
35/2
50/1
95/0
120/25
0MCM
Output
current
RELA
Y 2
130BB632.10
40
°
C
ambient
temperature
Continuous
(3
x
380-440
V)[A]
1.2
2.2
3.7
5.3
7.2
9.0
12.0
15.5
23.0
31.0
37.0
42.5
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent
(3
x
380-440
V)
[A]
1.3
2.4
4.1
5.8
7.9
9.9
13.2
17.1
25.3
34.0
40.7
46.8
67.1
80.3
99.0
116.0
161.0
194.0
Continuous
(3
x
440-480
V)[A]
1.1
2.1
3.4
4.8
6.3
8.2
11.0
14.0
21.0
27.0
34.0
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent
(3
x
440-480
V)
[A]
1.2
2.3
3.7
5.3
6.9
9.0
12.1
15.4
23.1
29.7
37.4
44.0
57.2
71.5
88.0
115.0
143.0
176.0
Max.
input
current
RELA
Y 2
130BB633.10
Continuous
(3
x
380-440
V)
[A]
1.2
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22.1
29.9
35.2
41.5
57.0
70.0
84.0
103.0
140.0
166.0
Intermittent
(3
x
380-440
V)
[A]
1.3
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.3
32.9
38.7
45.7
62.7
77.0
92.4
113.0
154.0
182.0
Continuous
(3
x
440-480
V)
[A]
1.0
1.8
2.9
3.9
5.3
6.8
9.4
12.6
18.4
24.7
29.3
34.6
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent
(3
x
440-480
V)
[A]
1.1
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.2
27.2
32.2
38.1
54.1
66.7
79.8
97.5
132.9
157.0
Max.
mains
fuses
See
5.1.4
Fuses
Quick Guide
VLT HVAC Basic Drive Quick Guide
36
MG18A302 - VLT
®