3.21.5 23-8* Payback Counter
The adjustable frequency drive includes a feature which can give a rough calculation on payback in cases where the adjustable frequency drive has been
installed in an existing plant to ensure energy savings by changing from fixed to variable speed control. Reference for the savings is a set value to represent
the average power yielded before the upgrade with variable speed control.
The difference between the Reference Power at fixed speed and the Actual Power yielded with speed control represent the actual savings.
As value for the fixed speed case, the rated motor size (kW) is multiplied with a factor (set in %) representing the power produced at fixed speed. The
difference between this reference power and the actual power is accumulated and stored. The difference in energy can be read in par.23-83
.
The accumulated value for the difference in power consumption is multiplied with the energy cost in local currency and the investment is subtracted. This
calculation for Cost Savings can also be read in par.23-84
Cost
Savings
=
{
∑
t
=0
t
(
Rated
Motor
Power
∗
Power
Reference
Factor
)
−
Actual
Power
Consumption
×
Energy
Cost
}
−
Investment
Cost
Break even (payback) occurs when the value read in the parameter turns from negative to positive.
It is not possible to reset the Energy Savings counter, but the counter can be stopped any time by setting par.23-80
to 0.
Parameter overview:
Parameter for settings
Parameters for readout
Rated Motor Power
Energy Savings
Power Reference Factor in %
Actual Power
Energy Cost per kWh
Cost Savings
Investment
23-80 Power Reference Factor
Range:
Function:
100 %*
[0 - 100 %]
Set the percentage of the rated motor size (set in par.1-20
) which is supposed to represent the average power yielded at the time running with
fixed speed (before upgrade with variable speed control).
Must be set to a value different from zero to start counting.