Mains Supply 3 x 525- 690V AC
P1M0
P1M2
P1M4
Typical Shaft output at 550 V [kW]
850
1000
1100
Typical Shaft output at 575 V [HP]
1150
1350
1550
Typical Shaft output at 690 V [kW]
1000
1200
1400
Enclosure IP21, 54 without/ with options
cabinet
F12/F13
F12/F13
F12/F13
Output current
Continuous
(at 550 V) [A]
1108
1317
1479
Intermittent (60 sec overload)
(at 550 V) [A]
1219
1449
1627
Continuous
(at 575/ 690 V) [A]
1060
1260
1415
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
1166
1386
1557
Continuous KVA
(at 550 V) [KVA]
1056
1255
1409
Continuous KVA
(at 690 V) [KVA]
1267
1506
1691
Max. input current
Continuous
(at 550 V ) [A]
1079
1282
1440
Continuous
(at 575 V) [A]
1032
1227
1378
Continuous
(at 690 V) [A]
1032
1227
1378
Max. cable size, motor [mm
2
(AWG
2)
)]
12x150
(12x300 mcm)
Max. cable size,mains F12 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,mains F13 [mm
2
(AWG
2)
)]
8x400
(8x900 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
6x185
(6x350 mcm)
Max. external mains fuses [A]
1
1600
2000
2500
Estimated power loss
at 600 V [W]
4)
15592
18281
20825
Estimated power loss
at 690V [W]
4)
16375
19207
21857
F3/F4 Max added losses CB or Disconnect &
Contactor
665
863
1044
Max panel options losses
400
Weight,
enclosure IP21, IP 54 [kg]
1246/ 1541
1246/ 1541
1280/1575
Weight, Rectifier Module [kg]
136
136
136
Weight, Inverter Module [kg]
102
102
136
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
85 °C
Power card ambient trip
68 °C
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to
variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line).frequency converter
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to
30W to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B,
each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be
allowed for (+/-5%).
Introduction
High Power Service Manual for Modular F Frame Drives
MG90K202 - VLT
®
is a registered Danfoss trademark
15
1
1