Parameter
Option/range
Default
Usage
Low Ref./Feedb.
Value
Parameter 6-25
Terminal 54
High Ref./
Feedb. Value
-4999–4999
50
Enter the feedback value that corresponds to the voltage or
current set in
parameter 6-21 Terminal 54 High Voltage
/
pa-
rameter 6-23 Terminal 54 High Current
.
Parameter 6-26
Terminal 54 Fil-
ter Time Con-
stant
0.00–10.00 s
0.01
Enter the filter time constant.
Parameter 6-29
Terminal 54
mode
[0] Current
[1] Voltage
[1] Voltage
Select if terminal 54 is used for current or voltage input.
Parameter
20-81 PI Nor-
mal/Inverse
Control
[0] Normal
[1] Inverse
[0] Normal
Select
[0] Normal
to set the process control to increase the
output speed when the process error is positive. Select
[1] In-
verse
to reduce the output speed.
Parameter
20-83 PI Start
Speed [Hz]
0–200 Hz
0 Hz
Enter the motor speed to be attained as a start signal for
commencement of PI control.
Parameter
20-93 PI Propor-
tional Gain
0.00–10.00
0.01
Enter the process controller proportional gain. Quick control
is obtained at high amplification. However, if amplification is
too high, the process may become unstable.
Parameter
20-94 PI Inte-
gral Time
0.1–999.0 s
999.0 s
Enter the process controller integral time. Obtain quick con-
trol through a short integral time, though if the integral time
is too short, the process becomes unstable. An excessively
long integral time disables the integral action.
Parameter
30-22 Locked
Rotor Detection
[0] Off
[1] On
[0] Off
–
Parameter
30-23 Locked
Rotor Detection
Time [s]
0.05–1.00 s
0.10 s
–
4.2.4 Motor Setup
The motor setup wizard guides users through the needed motor parameters.
Table 13: Motor Setup Wizard Settings
Parameter
Option/range
Default
Usage
Parameter 0-03
Regional Set-
tings
[0] International
[1] US
[0] Interna-
tional
–
Parameter 0-06
GridType
[0] 200–240 V/50 Hz/IT-grid
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT-grid
[11] 380–440 V/50 Hz/Delta
[12] 380–440 V/50 Hz
Size selected
Select the operating mode for restart after reconnection of
the drive to mains voltage after power down.
AQ367426199594en-000101 / 130R0988
36 | Danfoss A/S © 2021.06
Programming