Voltage [V]

Minimum waiting time (minutes)

4

7

15

20

30

40

200–240

1.1–3.7 kW

(1.50–5 hp)

5.5–45  kW

(7.5–60 hp)

380–480

1.1–7.5 kW

(1.50–10 hp)

11–90 kW

(15–121 hp)

315–1000 kW

(450–1350 hp)

400

90–315 kW

(121–450 hp)

500

110–355 kW

(150–500 hp)

525

75–315 kW

(100–450 hp)

525–600

1.1–7.5 kW

(1.50–10 hp)

11–90 kW

(15–121 hp)

690

90–315 kW

(100– 350 hp)

525–690

1.1–7.5 kW

(1.50–10 hp)

11–90 kW

(15–121 hp)

400–1400  kW

(500–1550 hp)

450–1400 kW

(600–1550 hp)

Table 1.1 Discharge Time, VLT

®

 HVAC Drive FC 102

Voltage [V]

Minimum waiting time (minutes)

4

7

15

20

40

200–240

0.25–3.7 kW

(0.34–5 hp)

5.5–37  kW

(7.5–50 hp)

380–480

0.25–7.5 kW

(0.34–10 hp)

11–75 kW

(15–100 hp)

110–315

(150–450 hp)

355–450

(500–600 hp)

355–560

(500–750 hp)

525–600

0.75–7.5 kW

(1.0–10 hp)

11–75 kW

(15–100 hp)

525–690

1.5–7.5 kW

(2–10 hp)

11–75 kW

(15–100 hp)

55–400

(75–400 hp)

450–630

(600–750 hp)

450–800

(600–950 hp)

Table 1.2 Discharge Time, VLT

®

 Refrigeration Drive FC 103

Voltage [V]

Minimum waiting time (minutes)

4

7

15

20

30

40

200–240

0.25–3.7 kW

(0.34–5 hp)

5.5–45  kW

(7.5–60 hp)

380–480

0.37–7.5 kW

(0.5–10 hp)

11–90 kW

(15–121 hp)

110–315 kW

(150–450 hp)

315–1000 kW

(450–1350 hp)

355–560 kW

(500–750 hp)

525–600

0.75–7.5 kW

(1–10 hp)

11–90 kW

(15–121 hp)

400–1400  kW

(400–1550 hp)

525–690

1.1–7.5 kW

(1.5–10 hp)

11–90 kW

(10–100 hp)

75–400 kW

(75–400 hp)

450–800 kW

(450–950 hp)

Table 1.3 Discharge Time, VLT

®

 AQUA Drive FC 202

Installation Instructions

Control Card VLT

®

 FC Series

2

Danfoss A/S © 03/2017 All rights reserved.

MI93A102