5.2.6 Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-19 T
erminal 37 Safe
Stop
[1] Safe Stop
Alarm
* = Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 5.10 Start/Stop Command with Safe Torque Off (STO)
Option
130BB805.12
Speed
Start/Stop (18)
Illustration 5.3 Start/Stop Command with Safe Torque Off
(STO)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function
Setting
Parameter 5-10 Terminal
18 Digital Input
[9]
Latched
Start
Parameter 5-12 Terminal
27 Digital Input
[6] Stop
Inverse
* = Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 5.11 Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Illustration 5.4 Latched Start/Stop Inverse
Application Set-up Examples
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.