3 Installation
3.1.1 Tools Required
In addition to the standard tool kit, the below listed tools
are recommended for installation of the panel.
Tools Required
•
Spreader bar capable of lifting up to 1000 lbs.
Max diameter 0.875 in.
•
Forklift, crane, hoist or other lifting device
capable of handling up to 1000 lbs. (Qualified
device operator available for operating the
equipment.)
•
Metric Socket Set: 7 to 19 mm
•
Socket Extensions: 4, 6, and 12 in
•
Torx driver set: T10 to T40
•
Torque wrench: 6 - 170 lbs-in
L1
L1
L2
L2
L3
L3
GND
91
92
93
Fuses
130BB460.10
Illustration 3.1 Drive Input Fuses
3.1.2 Branch Circuit Protection
CAUTION
BRANCH CIRCUIT PROTECTION REQUIRED
Provide branch circuit protection in accordance with the
National Electrical Code. Failure to provide branch circuit
protection in accordance with the NEC could result in
equipment or property damage.
3.1.3 Drive Fuses
If specified as an enclosure option, drive input fuses will be
factory installed in the enclosure. If not factory supplied,
they must be provided by the installer as part of instal-
lation (see
Illustration 3.1
).
3.1.4 Internal Option Panel Fuses
When applicable, use the specified fuse or an equivalent
replacement only for internal option panel fuses. Fuse
options include the drive disconnect and contactor fuses.
See the nameplate label (
Illustration 3.2
) on the inside
cover of the unit for option panel fuse ratings.
e
zi
S/
re
b
m
u
N
t
ra
P
re
r
u
tc
af
u
n
a
M
e
s
u
F
F12
F13
F15
F16
F00
F900,F901,F902
Ferraz-Shawmut
Ferraz-Shawmut
Ferraz-Shawmut
Bussmann
Bussmann
…
500V FA 5 A
500V FA 10 A
LPJ-25SP
LPJ-35SP
500V FA 4 A
600 VAC, 120 A, Class CC
130BD320.10
Illustration 3.2
3.2 Mechanical Installation
3.2.1 Lifting
Check the weight of the unit before attempting to lift.
Ensure that the lifting device is suitable for safely lifting
the panel. If necessary, plan for a hoist, crane or forklift
with appropriate rating to move the units.
3.2.2 Hoist or Overhead Lift
•
Use solid steel spreader bar for lifting. Slide
spreader bar through two (2) lifting rings on
drive. Lifting rings are 0.75 in (19 mm) in
diameter (see
Illustration 3.3
).
•
Connect spreader bar to a hoist or other lifting
device.
•
Lift unit slightly using lifting rings with weight
distributed evenly.
•
Remove skid and other supports from under
drive.
•
For floor mounting applications, a floor mounting
kit is available from Danfoss specifically designed
to anchor drive to floor.
Installation
Option Panel Operating Instructions
12
MG14I102 - VLT
®
is a registered Danfoss trademark