OL1 - Single Motor
OL1 - Dual Motor
OL2 - Dual Motor
CMS - M4 & M5
MT1 TB 0R LUG (ECB)
Type Code Char
CHAR 20
CHAR 20
CHAR 20
CHAR 20
CHAR 13&14&18
Type Code
S
D
D
C
NO&D
[HP]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
0.50
8
N/A
N/A
10
12
0.75
8
N/A
N/A
10
12
1
8
N/A
N/A
10
12
1.5
8
8
8
10
12
2
8
8
8
10
12
3
8
8
8
10
12
5
8
8
8
10
4
7.5
8
8
8
8
4
10
8
8
8
8
4
15
1/0
8
8
1/0
4
20
1/0
1/0 (15-30HP)
8 (0.5-10HP)
1/0
4
8 (0.5-10HP)
8 (0.5-10HP)
25
1
1 (15-30HP)
8 (0.5-10HP)
1/0
1
8 (0.5-10HP)
8 (0.5-10HP)
30
1
1 (15-30HP)
8 (0.5-10HP)
1/0
1
40
4/0
1/0 (15-30HP)
8 (0.5-10HP)
4/0
250KCM
1/0 (15-30HP)
1/0 (15-30HP)
50
4/0
4/0 (40-60HP)
8 (0.5-10HP)
4/0
250KCM
1/0 (15-30HP)
8 (0.5-10HP)
1/0 (15-30HP)
1/0 (15-30HP)
60
4/0
4/0 (40-60HP)
8 (0.5-10HP)
4/0
250KCM
4/0 (40-60HP)
1/0 (15-30HP)
1/0 (15-30HP)
1/0 (15-30HP)
Table 3.11 230 V Max Wire - Output
Installation
Option Panel Operating Instructions
MG14I102 - VLT
®
is a registered Danfoss trademark
21
3
3