Digital outputs
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0-24 V
Max. output current (sink or source)
40 mA
Max. load at frequency output
1 k
Ω
Max. capacitive load at frequency output
10 nF
Minimum output frequency at frequency output
4 Hz
Maximum output frequency at frequency output
32 kHz
Accuracy of frequency output
Max. error: 0.1 % of full scale
Resolution of frequency outputs
10 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
12
Max. load
100 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
2
Relay 01 and 02
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Max. terminal load (AC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
250 V AC, 3 A
Max. terminal load (AC-15)
1)
on 01-02/04-05 (NO) (Inductive load
@
cos
φ
0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
30 V DC, 2 A
Max. terminal load (DC-13)
1)
on 01-02/04-05 (NO) (Inductive load)
24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
250 V AC, 3 A
Max. terminal load (AC-15)
1)
on 01-03/04-06 (NC) (Inductive load
@
cos
φ
0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
30 V DC, 2 A
Min. terminal load on 01-03 (NC), 01-02 (NO)
24 V DC 10 mA, 24 V AC 20 mA
1) IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
Control card, +10 V DC output
Terminal number
50
Output voltage
10.5 V
±
0.5 V
Max. load
15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0-500 Hz
±
0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2 ms
Speed control range (open loop)
1:100 of synchronous speed
Speed accuracy (open loop)
30-4000 RPM: Maximum error of
±
8 RPM
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure type J1-J7
IP20, IP21/Type 1
Vibration test all enclosure types
1.0 g
Relative humidity
5-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
max. 55
°
C
1)
- at full continuous output current with some power size
max. 50
°
C
1)
- at full continuous output current
max. 45
°
C
1)
Specifications
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark
71