3.4.6 The Data Field
The structure of data blocks depends on the type of telegram. There are three telegram types, and the type applies for both
control telegrams (master
⇒
slave) and response telegrams (slave
⇒
master).
The 3 types of telegram are:
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words) and contains:
-
Control word and reference value (from master to slave)
-
Status word and present output frequency (from slave to master)
ADR
LGE
STX
PCD1
PCD2
BCC
130BA269.10
Illustration 3.4 Process Block
Parameter block
The parameter block is used to transfer parameters between master and slave. The data block is made up of 12 bytes (6
words) and also contains the process block.
PKE
IND
ADR
LGE
STX
PCD1
PCD2
BCC
130BA271.10
PWE
high
PWE
low
Illustration 3.5 Parameter Block
Text block
The text block is used to read or write texts via the data block.
PKE
IND
130BA270.10
ADR
LGE
STX
PCD1
PCD2
BCC
Ch1
Ch2
Chn
Illustration 3.6 Text Block
3.4.7 The PKE Field
The PKE field contains two subfields: Parameter command
and response (AK) and Parameter number (PNU):
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BB918.10
PKE
IND
PWE
high
PWE
low
AK
PNU
Par
amet
er
commands
and r
eplies
Par
amet
er
number
Illustration 3.7 PKE Field