3.
Use navigation keys to scroll to parameter group
0-0* Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Opperations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Figure 3.27 Operation/Display
4.
Use navigation keys to scroll to
0-03 Regional
Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Figure 3.28 Basic Settings
5.
Use navigation keys to select
[0] International
or
[1] North America
as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See
American Default Parameter Settings
for a
complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Use the navigation keys to scroll to parameter
group
Q2 Quick set-up
and press [OK].
130BB847.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
13.7% 13.0A 1(1)
Quick Menus
Figure 3.29 Quick Menus
8.
Select language and press [OK].
9.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave
5-12 Terminal 27 Digital Input
at factory
default. Otherwise select
No Operation
. For
adjustable frequency drives with an optional
Danfoss bypass, no jumper wire is required.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
12.
3-41 Ramp 1 Ramp-up Time
13.
3-42 Ramp 1 Ramp-down Time
14.
3-13 Reference Site
. Linked to Hand/Auto* Local
Remote.
3.4 Automatic Motor Adaptation
Automatic motor adaptation (AMA) is a test procedure that
measures the electrical characteristics of the motor to
optimize compatibility between the adjustable frequency
drive and the motor.
•
The adjustable frequency drive builds a
mathematical model of the motor for regulating
output motor current. The procedure also tests
the input phase balance of electrical power. It
compares the motor characteristics with the data
entered in parameters 1-20 to 1-25.
•
It does not cause the motor to run or harm to
the motor
•
Some motors may be unable to run the complete
version of the test. In that case, select
[2] Enable
reduced AMA
•
If an output filter is connected to the motor,
select
Enable reduced AMA
•
If warnings or alarms occur, see
•
Run this procedure on a cold motor for best
results
Start-up and Functional Tes...
VLT
®
Refrigeration Drive Instruction Manual
MG16J122 - VLT
®
is a registered Danfoss trademark
3-9