0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast.
NOTICE
Can cause PWM when coasted.
[0]
Off This function is not active.
[1]
*
On This function is active.
4.1.2 0-1* Define and Set-up Operations
A complete set of all parameters controlling the frequency
converter is called a set-up. The frequency converter
contains 2 set-ups: Set-up 1 and set-up 2. Furthermore, a
fixed set of factory settings can be copied into 1 or both
set-ups.
Some of the advantages of having more than 1 set-up in
the frequency converter are:
•
Run the motor in 1 set-up (active set-up) while
updating parameters in another set-up (edit set-
up).
•
Connect the 2 motors (1 at a time) to the
frequency converter. Motor data for the 2 motors
can be placed in the 2 set-ups.
•
Rapidly change settings of the frequency
converter and/or the motor while the motor runs.
For example, ramp time or preset references via
bus or digital inputs.
The active set-up can be set as multi set-up, where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
To copy set-up 1 to set-up 2, or copy set-up 2 to set-up 1,
use
. To avoid conflicting
settings of the same parameter within 2 different set-ups,
link the set-ups using
. Stop the
frequency converter before switching between set-ups
where parameters marked
not changeable during operation
have different values.
Parameters that are
not changeable during operation
are
marked
false
in
0-10 Active Set-up
Option:
Function:
Select the set-up in which the frequency
converter operates.
[1]
*
Set-up 1
Set-up 1 is active.
[2]
Set-up 2
Set-up 2 is active.
[9]
Multi Set-
up
Used for remote set-up selections via digital
inputs and the serial communication port. This
0-10 Active Set-up
Option:
Function:
set-up uses the settings from
0-11 Programming Set-up
Option:
Function:
The number of the set-up being edited is
shown in the LCP, flashing.
[1]
Set-up 1
Edit set-up 1
[2]
Set-up 2
Edit set-up 2
[9]
*
Active Set-up Edit parameters in the set-up selected via
digital I/Os.
0-12 Link Setups
Option:
Function:
If the set-ups are not linked, a change between
them is not possible while the motor runs.
[0]
Not
linked
When selecting a different set-up for operation,
the set-up change does not occur until the
motor is coasted.
[20]
*
Linked
Copies
not changeable during operation
parameters from 1 set-up to the other. It is
possible to switch set-ups while the motor runs.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in line 1,
left position.
[0]
No display value selected.
[37]
Display Text 1
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
[38]
Display Text 2
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
[39]
Display Text 3
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
[953]
Profibus Warning
Word
Shows PROFIBUS communication
warnings.
[1501] Running Hours
View the number of running hours of
the motor.
[1502] kWh Counter
View the mains power consumption
in kWh.
[1600] Control Word
View the Control Word sent from the
frequency converter via the serial
communication port in hex code.
Parameters
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
35