The ground leakage current is made up of several contributions and depends on various system configurations, including:
RFI filtering.
Motor cable length.
Motor cable shielding.
Drive power.
e3
0b
b9
55
.1
2
a
b
Motor cable length
Leakage current
Illustration 44: Influence of the Cable Length and Power Size on Leakage Current, Power Size a > Power Size B
The leakage current also depends on the line distortion.
e3
0b
b9
56
.1
2
THDv=0%
THDv=5%
Leakage current
Illustration 45: Influence of Line Distortion on Leakage Current
If the leakage current exceeds 3.5 mA, compliance with EN/IEC 61800-5-1 (power drive system product standard) requires special
care.
AJ330233902305en-000201 / 130R0596
64 | Danfoss A/S © 2021.05
Electrical Installation
Considerations
VLT® Compressor Drive CDS 803
Design Guide