The display is divided into three sections:
Top section (a)
Shows the status when in status mode or up to two
variables when not in status mode and in the case of
alarm/warning.
The number of the active set-up (selected as the active
set-up in
0-10 Active Set-up
) is shown. When programming
in another set-up than the active set-up, the number of
the set-up being programmed appears to the right in
brackets.
Middle section (b)
Shows up to five variables with related unit, regardless of
status. In the event of an alarm/warning, the warning is
shown instead of the variables.
It is possible to toggle between three status readout
displays by pressing [Status].
Operating variables with different formatting are shown in
each status screen.
Several values or measurements can be linked to each of
the displayed operating variables. The values/
measurements to be displayed can be defined via
parameters 0–20, 0–21, 0–22, 0–23, and 0–24.
Each value/measurement readout parameter selected in
parameters 0–20 to 0–24 has its own scale and number of
digits after a possible decimal point. Larger numeric values
are displayed with few digits after the decimal point.
Ex.: Current readout
5.25 A; 15.2 A 105 A.
Status display I
This readout state is standard after startup or initialization.
Press [Info] to obtain information about the value/
measurement linked to the displayed operating variables
(1.1, 1.2, 1.3, 2, and 3).
See the operating variables shown in the display in
. 1.1, 1.2 and 1.3 are shown in small size. 2 and 3
are shown in medium size.
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kW
7.83 A
0.000
53.2%
Status
Figure 5.2 Status Display I - Operating Variables
Status display II
See the operating variables (1.1, 1.2, 1.3, and 2) shown in
the display in
.
In the example, speed, motor current, motor power, and
frequency are selected as variables in the first and second
lines.
1.1, 1.2 and 1.3 are shown in small size. 2 is shown in large
size.
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW
5.25A
6.9Hz
Status
Figure 5.3 Status Display II - Operating Variables
Status display III
This state displays the event and action of the smart logic
control.
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW
0.86 A
State: 0 off 0 (off)
When: -
Do: -
Status
Figure 5.4 Status Display III - Operating Variables
NOTICE!
Status display III is not available on the filter LCP.
User Interface
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
45