Bit 11, Relay 01
Bit 11="0": Relay not activated.
Bit 11="1": Relay 01 activated if
Control word bit 11
is
chosen in
5-40 Function Relay
.
Bit 12, Relay 04
Bit 12="0": Relay 04 is not activated.
Bit 12="1": Relay 04 is activated if
Control word bit 12
is
chosen in
5-40 Function Relay
.
Bit 13/14, Selection of set-up
Use bits 13 and 14 to select from the four menu set-ups
according to
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
Table 10.20 Selection of Set-up
The function is only possible when
Multi Set--ups
is
selected in
0-10 Active Set-up
.
Make a selection in
8-55 Set-up Select
to define how Bit
13/14 gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15=’0’: No reversing.
Bit 15=’1’: Reversing. In the default setting, reversing is set
to digital in
8-54 Reverse Select
. Bit 15 causes reversing only
when Ser. communication, Logic OR, or Logic AND is
selected.
10.13.2 Status Word According to FC
Profile
Output freq.
STW
Bit
no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
Figure 10.16 STW Follower to Master
Bit
Bit=0
Bit=1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Triplock
07
No warning
Warning
08
Speed≠reference
Speed=reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=’0’: The adjustable frequency drive trips.
Bit 00=’1’: The adjustable frequency drive controls are
ready but the power component does not necessarily
receive any power supply (in case of external 24 V supply
to controls).
Bit 01, Drive ready
Bit 01=’1’: The adjustable frequency drive is ready for
operation but the coasting command is active via the
digital inputs or via serial communication.
Bit 02, Coasting stop
Bit 02=’0’: The adjustable frequency drive releases the
motor.
Bit 02=’1’: The adjustable frequency drive starts the motor
with a start command.