6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-10 Terminal 53 Low Voltage
to
parameter 6-12 Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in
to
parameter 6-13 Terminal 53 High
Current
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant. This is a first-order
digital low-pass filter time constant for
suppressing electrical noise in terminal 53.
A high time constant value improves
dampening, but also increases the time
delay through the filter.
6-19 Terminal 53 mode
Option:
Function:
Select whether terminal 53 is used for
current or voltage input.
[0]
Current mode
[1]
*
Voltage mode
4.7.3 6-2* Analog Input 54
Parameters for configuring the scaling and limits for analog
input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[0 - 10
V]
Enter the voltage (V) that corresponds to the
low reference value (set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value
). To activate
, set the value at >1 V.
6-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
*
[0 - 20
mA]
Enter the low current value. This reference
signal corresponds to the low reference/
feedback value, set in
. To activate the live
zero timeout function in
, set the value to >2 mA .
6-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[0 - 20
mA]
Enter the high current value corresponding
to the high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage
parameter 6-22 Terminal 54 Low Current
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in
parameter 6-23 Terminal 54 High
Current
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant, which is a first-
order digital low-pass filter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
dampening, but also increases the time
delay through the filter.
6-29 Terminal 54 mode
Option:
Function:
Select if terminal 54 is used for current
input or voltage input.
[0]
Current mode
[1]
*
Voltage mode
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
63