Parameter 1-10 Motor
Construction
[0]
Asynchro
-
nous
[1] PM
Motor
non-
salient
[2] PM
Motor
Salient
IPM
[3]
SynRM
Motor
Parameter 4-14 Motor
Speed High Limit [Hz]
x
x
x
x
Parameter 4-16 Torque
Limit Motor Mode
x
x
x
x
Parameter 4-17 Torque
Limit Generator Mode
x
x
x
x
x
x
x
x
Parameter 4-19 Max
Output Frequency
x
x
x
x
Parameter 4-58 Missing
Motor Phase Function
x
–
x
x
x
–
–
–
Parameter 14-41 AEO
Minimum Magneti-
sation
x
–
–
–
Parameter 14-42 Minim
um AEO Frequency
x
–
–
–
x
–
–
–
1-10 Motor Construction
Select the motor construction type.
Option:
Function:
[0]
*
Asynchron
For asynchronous motors.
[1]
PM, non salient SPM For permanent magnet (PM) motors.
PM motors are divided into 2 groups,
with either surface-mounted (non-
salient) or interior (salient) magnets.
[2]
PM, salient IPM
[5]
SynRM
3.3.3 Asynchronous Motor Set-up
Enter the following motor data. Find the information on
the motor nameplate.
1.
Parameter 1-20 Motor Power [kW]
or
parameter 1-21 Motor Power [HP]
2.
Parameter 1-22 Motor Voltage
.
3.
Parameter 1-23 Motor Frequency
4.
.
5.
Parameter 1-25 Motor Nominal Speed
.
For optimum performance in VVC
+
mode, extra motor data
is required to set up the following parameters. Find the
data in the motor datasheet (this data is typically not
available on the motor nameplate). Run a complete
automatic motor adaptation (AMA) using
parameter 1-29 Automatic Motor Adaptation (AMA)
[1]
Enable Complete AMA
or enter the parameters manually.
Parameter 1-36 Iron Loss Resistance (Rfe)
is always entered
manually.
1.
Parameter 1-30 Stator Resistance (Rs)
.
2.
Parameter 1-31 Rotor Resistance (Rr)
.
3.
Parameter 1-33 Stator Leakage Reactance (X1)
.
4.
Parameter 1-34 Rotor Leakage Reactance (X2)
5.
Parameter 1-35 Main Reactance (Xh)
.
6.
Parameter 1-36 Iron Loss Resistance (Rfe)
.
Application-specific adjustment when running VVC
+
VVC
+
is the most robust control mode. In most situations,
it provides optimum performance without further
adjustments. Run a complete AMA for best performance.
3.3.4 PM Motor Set-up
This section describes how to set up a PM motor.
Initial programming steps
To activate PM motor operation, select
[1] PM, non-salient
SPM
or
[2] PM, salient IPM
in
.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
43
3