6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings
).
•
Parameters associated with the terminals and
their settings are shown next to the drawings.
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
NOTICE!
When the optional Safe Torque Off feature is used, a
jumper wire may be required between terminal 12 (or
13) and terminal 37 for the adjustable frequency drive to
operate when using factory default programming values.
6.1 Application Examples
6.1.1 Feedback
Parameters
FC
4-20 mA
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A 54
U - I
+
-
130BB675.10
Function
Setting
6-22 Terminal 54
Low Current
4 mA*
6-23 Terminal 54
High Current
20 mA*
6-24 Terminal 54
Low Ref./Feedb.
Value
0*
6-25 Terminal 54
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
D IN 37 is an option.
Table 6.1 Analog Current Feedback Transducer
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A54
U - I
0 - 10V
+
-
130BB676.10
Function
Setting
6-20 Terminal 54
Low Voltage
0.07 V*
6-21 Terminal 54
High Voltage
10 V*
6-24 Terminal 54
Low Ref./Feedb.
Value
0*
6-25 Terminal 54
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
D IN 37 is an option.
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A54
U - I
0 - 10V
+
-
130BB677.10
Function
Setting
6-20 Terminal 54
Low Voltage
0.07 V*
6-21 Terminal 54
High Voltage
10 V*
6-24 Terminal 54
Low Ref./Feedb.
Value
0*
6-25 Terminal 54
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
D IN 37 is an option.
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
Application Set-up Examples
Instruction Manual
MG20MA22