Illustration 2.10 Motor, Mains and Earth Wiring for B-Frame Sizes
and Above Using Shielded Cable
130BB477.10
91
L1
92
L2
93
L3
96
U
97
V
99
W
88
DC+
89
DC-
91
R-
9
R+
95
99
Illustration 2.11 Motor, Mains and Earth Wiring for B-Frame Sizes
and Above Using Conduit
2.4.4 AC Mains Connection
•
Size wiring based upon the input current of the
frequency converter. For maximum wire sizes see
10.1 Power-dependent Specifications
•
Comply with local and national electrical codes
for cable sizes.
•
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see
•
Depending on the configuration of the
equipment, input power will be connected to the
mains input terminals or the input disconnect.
L 1 L 2
L 3
91
92
93
130B
T336.10
Illustration 2.12 Connecting to AC Mains
•
Ground the cable in accordance with grounding
instructions provided in
•
All frequency converters may be used with an
isolated input source as well as with ground
reference power lines. When supplied from an
isolated mains source (IT mains or floating delta)
or TT/TN-S mains with a grounded leg (grounded
delta), set
14-50 RFI Filter
to OFF. When off, the
internal RFI filter capacitors between the chassis
and the intermediate circuit are isolated to avoid
damage to the intermediate circuit and to reduce
earth capacity currents in accordance with IEC
61800-3.
2.4.5 Control Wiring
•
Isolate control wiring from high power
components in the frequency converter.
•
If the frequency converter is connected to a
thermistor, for PELV isolation, optional thermistor
control wiring must be reinforced/double
insulated. A 24V DC supply voltage is
recommended.