Current rating
380-415V, 50 and
60Hz
Current
rating
440-480V,
60Hz
Danfoss
Contactors for
AHF005 and
AHF010
Alternative
type AC3
A
A
Type
Contactor
rating
1)
KVAr
10
10
CI 9
1
14
14
CI 9
2
22
19
CI 9
4
29
25
CI 9
6
34
31
CI 16
7
40
36
CI 16
7
55
48
CI 16
9
66
60
CI 61
11
82
73
CI 61
15
96
95
CI 61
17
133
118
CI 61
22
171
154
CI 61
29
204
183
CI 61
36
251
231
CI 110
44
304
291
CI 110
51
325
355
CI 110
58
380
380
CI 110
66
480
436
CI 141
88
1)
min. 50% of the nominal load
6.2.3 Wiring
Supply voltage must be connected to the terminals X1.1, X1.2 and X1.3. The frequency converter supply terminals L1, L2 and L3
must be connected to the filter terminals X2.1, X2.2 and X2.3
Paralleling of frequency converters
If several frequency converters are to be connected to one harmonic filter, the connection method is similar to the connection
described above. The supply terminals L1, L2 and L3 of the frequency converters must be connected to the filter terminals X2.1,
X2.2 and X2.3.
NOTE
Use cables complying with local regulations.
Paralleling of filters
If the mains input current of the frequency converter exceeds the nominal current of the largest harmonic filter, several
harmonic filters can be paralleled to achieve the necessary current rating – see
Electrical Data
tabels.
Supply voltage be connected to the terminals X1.1, X1.2 and X1.3 of the filters. The frequency converter supply terminals L1, L2
and L3 must be connected to the filters terminals X2.1, X2.2 and X2.3
Terminals and cables
The following tabels show the terminal types, cable cross section, tightening torque, etc.
How to Install
AHF005/010 Design Guide
34
MG.80.C4.02 - VLT
®
is a registered Danfoss trademark
6
6
Summary of Contents for VLT AHF005
Page 1: ...MAKING MODERN LIVING POSSIBLE Design Guide AHF005 010 ...
Page 43: ......
Page 44: ......
Page 59: ...www danfoss com drives MG80C402 130R0436 MG80C402 Rev 2010 12 20 ...