AHF 005/010

Description

Description

The Danfoss harmonic filters AHF 005 and AHF 010

are ensuring near sinusoidal line current minimising

the harmonic current emission into the mains supply.

The Danfoss AHF 005 and AHF 010 are advanced

harmonic filters not to be compared with traditional

harmonic trap filters. The Danfoss harmonic filters

have been specially designed to match all the Danfoss

frequency converters. The filters AHF 010 and AHF

005 are available in two voltage ratings.

380 - 415 V AC

440 - 480 V AC

The Danfoss AHF 010 and AHF 005 have the

following characteristics:

Small compact housing that fits into a panel

Easy to use in retrofit applications

AHF 010 reduces the total harmonic current

distortion to 10%*

AHF 005 reduces the total harmonic current

distortion to 5%*

Current rating from 10A - 324A

For higher power modules can be paralleled

One filter module can be used for several

frequency converters

High efficiency (> 0.98)

User-friendly commissioning - no adjustment

necessary

No routine maintenance required

* THiD of 10% or 5% will be achieved when the

following conditions are met:

-

THvD of the system without the drive

operating is less than 2%

-

Filter is operating at nominal load

If these conditions are not fulfilled, a significant reduction

of the harmonic components can still be achieved, but

the rated THiD values may not be achieved.

Principle connection diagram of the
Danfoss harmonic filter.

Legends (as used throughout this manual):

U

L

:

Line voltage

I

AHF

:

Input current of the filter
AHF

I

FC,L

:

Input current to the
frequency converter

I

M

:

Motor current

MG.80.B2.02 - VLT is a registered Danfoss trademark

3

Summary of Contents for VLT AHF 005

Page 1: ...Drives Solutions www danfoss com drives InstructionManual Harmonic Filter AHF 005 010...

Page 2: ...ns weight 7 Dimension diagrams 8 Installation 10 Mechanical installation 10 Ventilation 10 Power wiring 10 Over temperature contactor 11 Power wiring size copper 12 Operation on different mains type 1...

Page 3: ...rrectly and used in accordance with their purpose Avoid filter module damage 1 The filter modules are to be used only with Danfoss frequency converters The usage with other electrical loads is not per...

Page 4: ...ortion to 10 AHF 005 reduces the total harmonic current distortion to 5 Current rating from 10A 324A For higher power modules can be paralleled One filter module can be used for several frequency conv...

Page 5: ...8150 289 A 132 160 175G6610 175G6632 5200 5250 6175 6225 8200 8250 324 A 175G6611 175G6633 Higher ratings can be achieved by paralleling the filter units 360 A 200 Two 180 A units 5300 6275 8300 434...

Page 6: ...rying from the input current ratings of VLT 5000 VLT 6000 and VLT 8000 series as stated in the respective operating instructions as these numbers are based on different operating conditions Calculatio...

Page 7: ...al load If these conditions are not or only partially fulfilled a significant reduction of the harmonic components can still be achieved but the rated THiD values may not be achieved Environmental dat...

Page 8: ...03 Kg 227 lbs 180 A E 107 Kg 236 lbs 217 A E 112 Kg 247 lbs 217 A E 119 Kg 262 lbs 289 A F 135 Kg 298 lbs 289 A F 145 Kg 320 lbs 324 A F 180 Kg 397 lbs AHF 005 380 415 V AC 50Hz AHF 005 440 480 V AC 6...

Page 9: ...AHF 005 010 Dimension diagrams Frame size B Frame size C Frame size D MG 80 B2 02 VLT is a registered Danfoss trademark 8...

Page 10: ...AHF 005 010 Specifications Frame size E Frame size F Frame size G MG 80 B2 02 VLT is a registered Danfoss trademark 9...

Page 11: ...536 W 43 A 463 W 72 A 898 W 72 A 776 W 101 A 1260 W 101 A 1089 W 144 A 1796 W 144 A 1553 W 180 A 2245 W 180 A 1941 W 217 A 2706 W 217 A 2340 W 289 A 3604 W 289 A 3116 W 324 A 3493 W NB If other heat s...

Page 12: ...lter becomes the sum of the individual current ratings Use cables complying with local regulations Over temperature contactor The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvani...

Page 13: ...This type of termination imposes no specifications of the minimum and maximum cable size suitable for connection Power terminal details regarding the bus bars can be found in the figures below Frame...

Page 14: ...m or thick grounding tapes Use copper or tinned copper screened wires only as steel screened wires are not suitable for high frequency applications Connect the screen with metal clamps or metal glands...

Page 15: ...t correct a non intended operation of controller and or filter module is possible First powering up 1 Switch on mains supply The filter module is ready for operation at once 2 Check the readiness of t...

Page 16: ...In particular during transport and handling no components are allowed to be bend and or isolating distances may not be altered The units are equipped with electrostatic sensitive devices which may be...

Page 17: ...ecause of possibly charged capacitors During operation all covers and doors must be closed 7 Maintenance and service The manufacturer s documentation must be observed This safety information must be k...