AHF 005/010

Mechanical installation

The encapsulation of the filters have an IP 20

rating. The modules can be mounted side by side

with 60mm (2,36 inches) clearance.

To other components and to the cabinet walls keep a

horizontal clearance of at least 70mm (2,76 inches) and

a vertical clearance of at least 150mm (5,91 inches).

For versions with bus bars (frame size E

– G) it is necessary to mount the added

covers to the connectors in order to

achieve the protection type IP 20.

Ventilation

The filters are cooled by means of air circulation.

Consequently, the air needs to be able to move freely

above and below the filter module. The efficiency

of the filter modules is greater than 0.98. When

installing a filter module in a panel or another enclosure,

ensure there is sufficient airflow though the enclosure

to limit heat rise in the enclosure.

AHF 0xx

380 – 415V

Max.
Heat

AHF 0xx

440 – 480V

Max.

Heat

10 A

108 W

19 A

236 W

19 A

205 W

26 A

324 W

26 A

280 W

35 A

436 W

35 A

377 W

43 A

536 W

43 A

463 W

72 A

898 W

72 A

776 W

101 A

1260 W

101 A

1089 W

144 A

1796 W

144 A

1553 W

180 A

2245 W

180 A

1941 W

217 A

2706 W

217 A

2340 W

289 A

3604 W

289 A

3116 W

324 A

3493 W

NB!:

If other heat sources (e.g. Danfoss frequency

converters) are installed in an enclosure

with the harmonic filter AHF 0xx, this

heat generation must also be considered when

calculating required airflow

NB!:

If the cooling air is polluted (dust, dirt swirl,

grease, aggressive gas) the function of

the filter module may be impeded. Ensure

sufficient countermeasures, e.g. separate cooling air,

mounting of air filters, periodical cleaning.

Power wiring

Standard connection

Supply voltage must be connected to the terminals

X1.1, X1.2 and X1.3. The frequency converter supply

terminals L1, L2 and L3 must be connected to the

filter module terminals X2.1, X2.2 and X2.3.

Paralleling of FC’s

If several frequency converters are to be connected

to the harmonic filter, the connection is similar to the

standard connection - The supply terminals L1, L2 and

L3 of several frequency converters must be connected

to the filter module terminals X2.1, X2.2 and X2.3.

MG.80.B2.02 - VLT is a registered Danfoss trademark

10

Summary of Contents for VLT AHF 005

Page 1: ...Drives Solutions www danfoss com drives InstructionManual Harmonic Filter AHF 005 010...

Page 2: ...ns weight 7 Dimension diagrams 8 Installation 10 Mechanical installation 10 Ventilation 10 Power wiring 10 Over temperature contactor 11 Power wiring size copper 12 Operation on different mains type 1...

Page 3: ...rrectly and used in accordance with their purpose Avoid filter module damage 1 The filter modules are to be used only with Danfoss frequency converters The usage with other electrical loads is not per...

Page 4: ...ortion to 10 AHF 005 reduces the total harmonic current distortion to 5 Current rating from 10A 324A For higher power modules can be paralleled One filter module can be used for several frequency conv...

Page 5: ...8150 289 A 132 160 175G6610 175G6632 5200 5250 6175 6225 8200 8250 324 A 175G6611 175G6633 Higher ratings can be achieved by paralleling the filter units 360 A 200 Two 180 A units 5300 6275 8300 434...

Page 6: ...rying from the input current ratings of VLT 5000 VLT 6000 and VLT 8000 series as stated in the respective operating instructions as these numbers are based on different operating conditions Calculatio...

Page 7: ...al load If these conditions are not or only partially fulfilled a significant reduction of the harmonic components can still be achieved but the rated THiD values may not be achieved Environmental dat...

Page 8: ...03 Kg 227 lbs 180 A E 107 Kg 236 lbs 217 A E 112 Kg 247 lbs 217 A E 119 Kg 262 lbs 289 A F 135 Kg 298 lbs 289 A F 145 Kg 320 lbs 324 A F 180 Kg 397 lbs AHF 005 380 415 V AC 50Hz AHF 005 440 480 V AC 6...

Page 9: ...AHF 005 010 Dimension diagrams Frame size B Frame size C Frame size D MG 80 B2 02 VLT is a registered Danfoss trademark 8...

Page 10: ...AHF 005 010 Specifications Frame size E Frame size F Frame size G MG 80 B2 02 VLT is a registered Danfoss trademark 9...

Page 11: ...536 W 43 A 463 W 72 A 898 W 72 A 776 W 101 A 1260 W 101 A 1089 W 144 A 1796 W 144 A 1553 W 180 A 2245 W 180 A 1941 W 217 A 2706 W 217 A 2340 W 289 A 3604 W 289 A 3116 W 324 A 3493 W NB If other heat s...

Page 12: ...lter becomes the sum of the individual current ratings Use cables complying with local regulations Over temperature contactor The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvani...

Page 13: ...This type of termination imposes no specifications of the minimum and maximum cable size suitable for connection Power terminal details regarding the bus bars can be found in the figures below Frame...

Page 14: ...m or thick grounding tapes Use copper or tinned copper screened wires only as steel screened wires are not suitable for high frequency applications Connect the screen with metal clamps or metal glands...

Page 15: ...t correct a non intended operation of controller and or filter module is possible First powering up 1 Switch on mains supply The filter module is ready for operation at once 2 Check the readiness of t...

Page 16: ...In particular during transport and handling no components are allowed to be bend and or isolating distances may not be altered The units are equipped with electrostatic sensitive devices which may be...

Page 17: ...ecause of possibly charged capacitors During operation all covers and doors must be closed 7 Maintenance and service The manufacturer s documentation must be observed This safety information must be k...

Page 18: ......

Reviews: