0-20 Display Line 1.1 Small
Option:
Function:
[1692]
Warning Word
One or more warnings in a
Hex code.
[1693]
Warning Word 2
One or more warnings in a
Hex code.
[1694]
Ext. Status Word
One or more status conditions
in a Hex code.
[3430]
PCD 10 Read from MCO
[30100] Digital Inputs
[30101] Digital Outputs
[30102] Commanded Position
[30103] Slave Index Position
[30104] Curve Position
[30107] Synchronizing Error
[30108] Actual Master Velocity
[30109] Axis Status
[30110] MCO 302 Status
[30120] MCO 302 Control
[30121] MCO Alarm Word 1
[30122] MCO Alarm Word 2
[30123] Idle time
[30124] Paramdb requests in
queue
[30130] tCon1 time
[30131] tCon2 time
[30132] Time Optimize Measure
[30133] HS Temp. (PC1)
[30134] HS Temp. (PC2)
[30135] HS Temp. (PC3)
0-21 Display Line 1.2 Small
Option:
Function:
[0]
*
None Select a variable for display in line 1, middle
position. The options are the same as listed for
0-20 Display Line 1.1 Small
.
0-22 Display Line 1.3 Small
Option:
Function:
[30120]
*
Mains Current
[A]
Select a variable for display in line 1,
right position. The options are the
same as listed for
0-20 Display Line 1.1
Small
.
0-23 Display Line 2 Large
Option:
Function:
[30100]
*
Output Current
[A]
Select a variable for display in line 2.
The options are the same as listed for
0-20 Display Line 1.1 Small
.
0-24 Display Line 3 Large
Select a variable for display in line 3.
Option:
Function:
[30121]
*
Mains Frequency The options are the same as those
listed in
0-20 Display Line 1.1 Small
.
0-25 My Personal Menu
Range:
Function:
Application
dependent
*
[0 -
9999 ]
Define up to 50 parameters to appear in
the Q1 Personal Menu, accessible via
the [Quick Menu] key on the LCP. The
parameters will be displayed in the Q1
Personal menu in the order they are
programmed into this array parameter.
Delete parameters by setting the value
to ‘0000’.
For example, this can be used to
provide quick, simple access to just one
or up to 50 parameters which require
changing on a regular basis (e.g., for
plant maintenance reasons) or by an
OEM to enable simple commissioning of
their equipment.
6.3.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on
the LCP.
6.3.6 0-40 [Hand on] Key on LCP
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled No effect when [Hand on] is pressed. Select [0]
Disabled to avoid accidental start of the
Adjustable frequency drive in
Hand on
mode.
[1]
*
Enabled
[2]
Password Avoids unauthorized stop. If
is included in the Quick Menu, then define the
password in
.
0-41 [Off] Key on LCP
Option:
Function:
[0]
*
Disabled Avoids accidental stop of the unit.
[1]
*
Enabled
[2]
Password Avoids unauthorized stop. If
is included in the Quick Menu, then define the
password in
.
How to Program
VLT Active Filter AAF 00x
6-8
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6