Introduction

The Danfoss BACLink® is a microprocessor based communication

portal that provides seamless translation between BACnet and

Danfoss VLTs. The portal supports BACnet communications
through Ethernet, BACnet IP over Ethernet (often referred to as

Ethernet IP), ARCnet, EIA-485 (using MS/TP), or EIA-232 (PTP).

The BACLink portal provides a dedicated Ethernet port and two

serial communication ports which can be configured for different

protocols. Baud rates are software selectable. An optional EIA-485

4-wire connection is also available to extend network cable length
beyond 4000 feet.

Do not input multiple protocol formats to the portal at the same time

since this can cause a communications loop and generate

excessive electrical noise.

BACLink accesses the Johnson Controls Metasys®

 

 N2 protocol

resident in the Danfoss VLT® 

 

2800 and VLT® 6000 Adjustable

Frequency Drives. The BACLink port operates with an internal

ARCnet operating protocol. Recommended connection is through

EIA-485 compatible, half duplex, 9600 baud, shielded twisted-pair

wiring. Data points in the N2 database are classified as analog I/O

(floating point), binary I/O or integer data points. Each data type

has a unique structure defined in the Metasys N2 system 

Protocol

Specification for Vendors.

An appendix at the back of this manual contains the drive point

maps for BACnet.

About this manual

The information in this manual is intended to provide

comprehensive information on installation and set up of the VLT for
communication over a BACnet network.

It is assumed that the user has knowledge of the capabilities of the

BACnet network in addition to an understanding of the Danfoss

VLT 2800 and VLT 6000 drives. For specific information on

operation of the drive, refer to the 

Installation, Operation and

Maintenance Manual for the VLT 6000 

or the 

Operating

Instructions for the VLT 2800.

References

In addition to this manual, the following manuals may be

referenced:

Installation, Operation and Maintenance Manual for the
VLT

®

 

6000 Adjustable Frequency Drive

, Danfoss Graham

number 23-6108-00.

Operating Instructions for the

 

VLT

 

® 2800, Danfoss number

MG28Axxx

Johnson Controls Metasys

®

 

 N2 System Protocol Specification

for Vendors

, Johnson Controls number 04-3402-22.

Trademarks

Metasys® N2 is a Johnson Controls Inc registered trademark.

VLT® is a Danfoss registered trademark.

Summary of Contents for VLT 6000 series

Page 1: ...Instruction Manual BACLink VLT 6000 and VLT 2800 Adjustable Frequency Drives 176U7869 10 02...

Page 2: ...ave fully discharged wait 14 minutes after power has been removed before touching any internal component DANGER Copyright 2002 Danfoss Graham WARNING Warnings Against Unintended Start 1 While the driv...

Page 3: ...tart up 10 Changing VLT 6000 parameter data 10 VLT 2800 network connection 11 VLT 2800 BACnet start up 11 Changing VLT 2800 parameter data 11 Ethernet network connection 12 Wiring 12 Set IP address of...

Page 4: ...ints in the N2 database are classified as analog I O floating point binary I O or integer data points Each data type has a unique structure defined in the Metasys N2 system Protocol Specification for...

Page 5: ...s used to enable selection of IP address module address and network type Sw1 and Sw2 are disabled in VLTcommunication applications Keypad Display port Access port for optional keypad Port 2 Preferred...

Page 6: ...an enclosure mount the unit in an enclosed panel using the mounting holes provided on the BACLink portal backplate refer back to Figure 1 Leave about 2 inches 5 centimeters on each side for wiring acc...

Page 7: ...3 BACLink Enclosure Electrical Components Electrical wiring 1 Power must be supplied to the 115 VAC outlet from an external source see Figure 3 2 Plug transformer into 115 VAC outlet 3 Connect transfo...

Page 8: ...P and terminal 69 N on main control board of drive see figure 5 2 If shielded cabling is used connect one end of shield to terminal 61 This terminal is connected to ground via an internal RC link For...

Page 9: ...9600 for N2 protocol 503 Coasting LOGIC OR 504 DC brake LOGIC OR 505 Start LOGIC OR 506 Reversing DIGITAL INPUT 507 Select setup LOGIC OR 508 Select speed LOGIC OR 560 Override release time OFF The va...

Page 10: ...or details on changing parameters and programming the drive The appendix in this manual lists point maps for BACnet Changing VLT 2800 parameter data Use the VLT2800 keypad to access the Menu Mode and...

Page 11: ...nfiguration jumpers Procedure 1 Wiring Wire Connections Each BACLink portal can support up to 10 drives see Figure 7 Any mix of VLT 2800 or VLT 6000 drives is supported The preferred portal to drive w...

Page 12: ...the portal network address using the rotary switches 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 s digit 1 s digit Figure 8 BACLink DIP Switches Figure 9 Rotary Address Switches C Set BACLink portal a...

Page 13: ...es see Figure 14 6 Set BACLink portal address DIP switch BACLink portal DIP switch 5 refer back to Figure 1 must correspond to device instance number setting Set switch to 0 for addresses 0 to 99 or t...

Page 14: ...7 5 Plug EIA 485 configuration jumper to 2 wire position as shown in Figure 17 7 Wire to drives from BACLink port 2 from Net to drive terminal 68 and Net to drive terminal 69 Figure 17 Port 2 Configur...

Page 15: ...19 4 Plug EIA 485 232 configuration jumper to EIA 232 position as shown in Figure 20 5 Wire to drives from BACLink port 2 from Net to drive terminal 68 and Net to drive terminal 69 EIA 232 network con...

Page 16: ...n SYMPTOM CAUSE SOLUTION Transmit LED ON steady and receive LED OFF Reversed polarity to drive or short in EIA 485 cable Reverse wires to drive terminals 68 and 69 or remove short Transmit LED blinks...

Page 17: ...lows resetting drive after a fault that does not require cycling power Reset occurs at transition from OFF to ON 0 Off 1 On jog_ Used to start and run drive at a frequency set in parameter 209 0 Off 1...

Page 18: ...y vlt6000_prop_gain_ PID proportional gain for VLT 6000 only 0 00 to10 00 423 VLT 6000 only vlt6000_int_time_ PID integration time for VLT 6000 only 0 01 to 9999 00 sec 424 VLT 6000 only vlt6000_fb_fi...

Page 19: ...r_volt_ VAC Voltage being supplied to motor 517 524 dc_bus_volt_ VDC DC bus voltage of drive 518 525 therm_motor_load_ Calculated thermal load on motor Trip point is 100 519 526 therm_inverter_load_ C...

Page 20: ...ng 531 540 current_high_ 0 OK 1 Warning 531 540 feedback_low_ 0 OK 1 Warning 531 540 feedback_high_ 0 OK 1 Warning 531 540 live_zero_error_ 0 OK 1 Warning 531 540 phase_loss_ 0 OK 1 Warning 531 540 dr...

Page 21: ..._32_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_29_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_27_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_19_ 0 Off 1 On for...

Page 22: ...am Division of Danfoss Inc 8800 West Bradley Road P O Box 245041 Milwaukee Wisconsin 53224 9541 Phone 414 355 8800 Fax 414 355 6117 Toll free 800 621 8806 E mail graham grahamdrives com http www namc...

Reviews: