Address Input Selection
The Modbus RTU option card interface to
the VLT 6000 Adjustable Frequency Drive FC
protocol requires drive parameter values
selected as shown. They are the default
settings for those parameters and probably
require no change to operate the drive using
Modbus. The Modbus RTU option card
always transmits to the drive in which it
resides as address one (001). See the
VLT
6000 Operating Instructions
for details on
selecting and changing parameter values, if
necessary.
VLT 6000
Parameter
Settings
• Parameter 500,
Protocol
: FC protocol
• Parameter 501,
Address
: 001
• Parameter 502,
Baud Rate
: 9600 baud
The Modbus RTU option card has an address
and termination 9-input DIP switch. The
Modbus network address for the VLT 6000 is
set by DIP switch positions on the switch. Pin
9 is an ON/OFF switch for network termination.
DIP switch positions are read on power-up only,
so position changes will not be recognized until
the next power-up.
Modbus RTU
Option Card
Network
Address
Settings
• Set the Modbus address for the VLT 6000
in accordance with the table below. The
default input setting is for ADDRESS 1 and
termination ON.
Address and Termination
1
2
3
4
5
6
7
8
9
OFF
ON
O P E N
PCB EDGE