Hp to kW Chart
• 1 Hp = 0.746kW
• Each VLT 5000 can be under sized by 4 and over
sized by 1 – but watch current limits.
• This chart shows most of the Parameter 102 settings
Model
Hp
kW
Model
Hp
kW
0.25
0.18
5032
30.0
22.0
0.33
0.25
5042
40.0
30.0
0.50
0.37
5052
50.0
37.0
0.75
0.55
5062
60.0
45.0
5001
1.0
0.75
5075
75.0
55.0
5002
1.5
1.1
5100
100.0
75.0
5003
2.0
1.5
5125
125.0
90.0
5004
3.0
2.2
5150
150.0
110.0
5005
4.0
3.0
5200
200.0
132.0
5006
5.0
4.0
5250
250.0
160.0
5008
7.5
5.5
5300
300.0
200.0
5011
10.0
7.5
5350
350.0
250.0
5016
15.0
11.0
5450
450.0
315.0
5022
20.0
15.0
5500
500.0
355.0
5027
25.0
18.5
The drive takes all size information in kilowatts (kW), so horsepower (Hp) must be converted
to kW. The formula is 1 Hp = ¾ of a kW. The chart above shows the equivalent.
Each drive size can be programmed to accommodate 4 sizes smaller and one size larger.
On the larger size – do not exceed the maximum current rating of the drive.
Parameter 102 in the Instruction Manual shows all the kW sizes.